Sutron Corporation X-Link Operations & Maintenance Manual, Rev 1.63 5/24/2016 pg. 116
Event
Description
Tx Good
Condition:
A transmission is successfully completed.
Time logged:
The time the transmission processes
started
, which may be
minutes before it completed, depending on signal strength.
Value logged:
The total number of good transmissions made.
Tx Fail
Condition :
A transmission fails.
Time logged:
The time the transmission processes
started
. The reason why
the transmission failed is logged too: No modem detected,
communication error with modem, no signal, cannot register,
server not found.
Value logged:
The total number of bad transmissions made.
Tx Missing
Condition:
Logged by a backup system when the modem fails to complete
the transmission in time allocated. This indicates a problem
with either the software of the communication to the modem.
Time logged:
Value logged:
Trying
Backup
Condition:
X-Link could not connect to the main server and there is a
backup server setup.
Time logged:
Value logged:
Messages
Received
Condition:
The number of messages received by X-Link today.
Time logged:
Midnight
Value logged:
Client
Connect
Condition:
A remote connection is established with a listening X-Link.
Time logged:
Value logged:
Modem
Bytes Tx
Total
Condition:
The number of bytes transmitted during the lifetime of the
station (or at least since they were last cleared.)
Time logged:
Once a day at midnight
Value logged:
Modem
Bytes Rx
Total
Condition:
The number of bytes received during the lifetime of the station
(or at least since they were last cleared).
Time logged:
Once a day at midnight.
Value logged:
Modem
Bytes Tx
Today
Condition:
The number of bytes transmitted during the day.
Time logged:
Once a day at midnight
Value logged:
Modem
Bytes Rx
Today
Condition:
The number of bytes received during the day.
Time logged:
Once a day at midnight
Value logged:
Time
Before
Change
Condition:
.
Logged before the clock is changed
Time logged:
Value logged:
Time After
Change
Condition:
Logged after the clock is changed along with the number of
seconds that the clock was adjusted by. A negative number of
seconds implies the clock was set back.
Time logged:
Value logged: