Sutron Corporation X-Link Operations & Maintenance Manual, Rev 1.63 5/24/2016 pg. 105
To have an absolute temperature reading, you must measure the temperature of
the terminal strip and then add to it the thermocouple temperature.
K-Type Equations:
Linear delta T range of ± 20°C. Approximation error is ±0.20°C.
Temp (°C) = 25.346 * X*1000 – 0.1114 + Terminal_temp
Linear delta T range of ± 40°C. Approximation error is ±0.83°C.
Temp (°C) = 25.419 * X*1000 – 0.3847 + Terminal_temp
3
rd
order Poly delta T range of ± 20°C. Approximation error is ±0.01°C
Temp (°C) = Poly((X*1000), (Terminal_temp -0.0107), 25.263, -0.4443, 0.2053)
3
rd
order Poly delta T range of ± 40°C. Approximation error is ±0.03°C
Temp (°C) = Poly((X*1000), (Terminal_temp -0.0115), 25.326, -0.4305, 0.0861)
T-Type Equations:
Linear delta T range of ± 20°C. Approximation error is ±0.30°C.
Temp (°C) = 25.892 * X*1000 – 0.151 + Terminal_temp
Linear delta T range of ± 40°C. Approximation error is ±1.20°C.
Temp (°C) = 25.851 * X*1000 – 0.612 + Terminal_temp
3
rd
order Poly delta T range of ± 20°C. Approximation error is ±0.01°C
Temp (°C) = Poly((X*1000), (Termina 0.0051), 25.881, -0.688, 0.0277)
3
rd
order Poly delta T range of ± 40°C. Approximation error is ±0.03°C
Temp (°C) = Poly((X*1000), (Termina 0.0234), 25.868, -0.755, 0.0616)
8.5.
Tipping Bucket
This section describes how to physically connect the sensor and how to configure
the setup in X-Link.
The sensor used in this example is a standard switch closure tipping bucket. This
sensor closes a switch for each tip of the bucket and has two leads, polarity
doesn’t matter.
To wire it up, connect like so (The lead numbers are not marked with numbers;
this is just a reference.)