65
8.1
Integrating the SD3-A1 with external wiring with relays and
eightfold zone pair changeover
In this connection example, the restart interlock function is provided by the connected
command unit “start interlock”, which applies the voltage of 24V to the input RESTART
X1-2. The
SD3-A1
itself must be configured using the “
SD3SOFT
” user software so that
the operating mode “with restart interlock” is active.
Fig. 8.1-1:
Wiring the
SD3-A1
with evaluation of the OSSDs, zone pair changeover
and restart interlock (example)
Relays K1 and K2 must have forced contacts. They are operated directly at the two
failsafe semiconductor outputs OSSD 1 (X1-12) and OSSD 2 (X1-11).
Relay K3 has a deenergizing delay. A suitable mechanism must be provided for
extinguishing sparks. Please note that doing this will cause the switching time to be
extended.
Channels “x” and “y” must be integrated for Category 3 in accordance with DIN EN 954-1.
Integrating one channel based on “z” is only permitted with a one-channel control system
and taking into consideration the results of a risk analysis.
Serial machine controls are admissible only insofar the valid regulations allow.
Содержание SD3-A1
Страница 1: ......
Страница 12: ...12...
Страница 40: ...40 Fig 5 4 5 Considering the maximum measurement distance when safeguarding an area...
Страница 60: ...60 Fig 6 2 1 Example of a zone pair changeover for an AGV on a curved route...
Страница 61: ...61 Fig 6 2 2 Example of zone pair changeover with combined with reducing speed of the AGV...
Страница 101: ...101 13 13 Dimensional drawings of the SD3 A1...
Страница 102: ...102 13 14 Dimensional drawings of the mounting system...
Страница 106: ......