79
5.3.6 DC/DC Fault List
table 5-10 DC/DC Fault List
No.
Fault name
Common causes
Corrective measures
1
Fan alarm
fault
When the speed of one of
the fans falls below 400
rpm for one minute.
•
Check that the control board
fan interface terminals are well
connected; if they are, the fan
itself may be the problem.
2
Bus-side
soft start
fault and
contactor
fault
•
Busbar soft start fault:
After the busbar side
slow
start
contactor
has
absorbed,
the
voltage
difference
between the inner and
outer
side
exceeds
150V and is maintained
for 30s.
•
Busbar contactor fault:
After the busbar side
contactor
has
absorbed, the voltage
difference between the
inside
and
outside
voltage exceeds 30V
and is maintained for
30s.
•
Check that the control board
terminals are well connected, if
they are, it may be a problem
with the contactor body.
3
Battery side
soft start
failure and
contactor
failure
•
Battery soft start fault:
After the battery side
slow
start
contactor
has been activated, the
voltage
difference
between the inner and
outer
side
exceeds
150V and is maintained
for 30s.
•
Battery contactor fault:
After the battery side
contactor
has
been
absorbed, the voltage
difference between the
inner and outer side
exceeds 30V and is
maintained for 30s.
•
Check that the control board
and the battery side filter board
terminals are well connected, if
they are, the contactor body
may be the problem.