76
No.
Alarm name
Common causes
Corrective measures
10
Electric
heating failure
Electric
heating fault
lockout
•
Loose
wiring
or
broken cables in the
electrical control of
the electric heating.
•
Electrical
heating
failure.
•
Tighten
the
electric
control
wiring or replace the cable.
•
Replace the electric heating.
11
Ambient
temperature
sensing
failure
Discharge
temperature
sensing
failure
Inlet water
temperature
sensor failure
Inhalation
sensor failure
Condensation
temperature
sensor failure
Exhaust
temperature
sensor failure
•
The
electrical
control wiring of the
temperature sensor
is loose or the cable
is damaged.
•
Temperature sensor
failure.
•
Tighten the electrical control
wiring or replace the cable.
•
Replace the temperature sensor.
12
1# high
pressure
pressure
sensor failure
2# high
pressure
pressure
sensor failure
•
The
electrical
control wiring of the
pressure sensor is
loose or the cable is
damaged.
•
Pressure
sensor
failure.
•
Tighten the electrical control
wiring or replace the cable.
•
Replace the pressure sensor.
Operation & Maintenance Instruction