86
No.
Fault name
Common causes
Corrective measures
18
DC/DC
inductor
current 5
overcurrent
Inductive current 5
overcurrent.
Same as 15
19
DC/DC
inductor
current 6
overcurrent
Inductive current 6
overcurrent.
Same as 14
20
DC/DC
inductor
current
imbalance1
The current of the DC/DC
inductor current 1 is
unbalanced, and the
hardware is abnormal.
Power off and restart, if the fault
persists, replace the power board.
21
DC/DC
inductor
current
imbalance2
The current of the DC/DC
inductor current 2 is
unbalanced, and the
hardware is abnormal.
Power off and restart, if the fault
persists, replace the power board.
22
DC/DC
inductor
current
imbalance3
The current of the DC/DC
inductor current 3 is
unbalanced, and the
hardware is abnormal.
Power off and restart, if the fault
persists, replace the power board.
23
Battery
contactor
failure
Based on the detection
logic, the relay is judged to
be either broken or short-
circuited (the voltage
difference between the
internal and external
sampling voltage exceeds
30V).
•
Check
if
the
contactor
is
operating:
replace
the
contactor.
•
Is the wiring correct.
•
Is the 12V supply normal and
the slow start MOS board:
replace the control board.
•
Test the power board BAT +
and BAT- for a short circuit:
Replace the power board.