73
No.
Fault name
Common causes
Corrective measures
•
Liquid temperature set too high, no
cooling required, check inlet and return
liquid temperatures and set appropriate
control temperature.
•
Stop time delay, the compressor has a
minimum stop time in normal conditions
and if the temperature rises to the start
point during this time, the compressor
will still turn on with a delay.
•
The condenser is dirty and blocked,
flush
the
condenser
and
end
the
cleaning when the water discharged
from the drain hole is clear at the edge.
•
The external circulation fan does not
run, refer to "Fan failure" in the "Fan
does not run" fault to deal with.
3
Failure of
the coolant
circulation
system
The coolant
system does not
circulate properly.
•
Without power on (standby), check the
main power switch and check the
operating display screen that it is
switched on.
•
Loose circuit connections, tighten circuit
connectors.
•
Water pump inverter failure, replace
water pump inverter.
•
No coolant causes the water pump to
protect itself, check if there is coolant in
the circulation system, if not make up
for it.
•
Pump body failure, replace pump.
•
Heating setpoint too low, no heating
required, check that the discharge
temperature and heating setpoint are
set reasonably.
•
Loose circuit connections, tighten circuit
connectors.
•
Electric heating overheating protection,
wait for a period of time and then restart
the electric heating and observe if the
electric heating is working properly.
•
Failure of the electric heating of the
pipes,
replacement
of
the
electric
heating.