8
Item
Check method
Air inlet and outlet
Check the temperature of the radiator and the amount of dust
accumulated. Clean heat-dissipation modules with a vacuum
cleaner if necessary.
Wiring and cable
layout
Completely power off the devices inside the BESS before checking.
For any non-conformances found during inspection, correct them
immediately.
•
Check whether the cable layout is normal and whether there is a
short circuit. For any non-conformances found during inspection,
correct them immediately.
•
Check whether all cable entry are well sealed.
•
Check whether there is water seepage inside the BESS.
•
Check whether the power cables are loose, and fasten them
again by the torque specified previously.
•
Check whether the power cables and control cables are
damaged, especially if the surface contacting the metal surface is
cut.
•
Check whether the insulation tapes on the power cable terminals
fall off.
Ground
connection and
equipotential
connection
•
Check whether the ground connection is correct and the
grounding resistance shall be no more than 4Ω.
•
Check whether the equipotential connection inside the integrated
BESS is correct.
Fan
•
Check the running status of fans.
•
Check whether fans are blocked.
•
Check if there is abnormal noise during operation of the fans.
Screw
Check whether internal screws fall off.
3.2.3 Maintenance (Every half a year to once a year)
Item
Check method
Safety function
•
Check whether the shutdown key on the touchscreen and the
emergency stop button work normally.
•
Simulate shutdown.
•
Check the warning marks and other device marks, and replace
them timely when they are fuzzy or damaged.
Software
maintenance
Check the settable parameters on the Web.
Operation & Maintenance Instruction
Содержание ST2752UX
Страница 2: ......
Страница 7: ...V Unless otherwise specified devices in this manual are referred to as the abbreviations above...
Страница 8: ......
Страница 105: ...www sungrowpower com Sungrow Power Supply Co Ltd...