5.3.5 Temperature Control System Fault/Alarm List
table 5-8 Temperature Control System Fault List
No.
Fault name
Common causes
Corrective measures
1
Fan failure
The blower does
not operate
properly.
•
Circuit breaker tripped, check if the
circuit breaker inside the chiller is
closed.
•
If the power input is abnormal (e. g.
overvoltage or undervoltage), check the
chiller for corresponding alarms and
refer to "Alarm Handling" to deal with
them.
•
Blower stuck, check for foreign objects
stuck in the blower.
•
Loose terminals, check for loose fan
docking terminals.
•
Compressor does not start, see "-
Compressor
does
not
start"
in
"-
Refrigeration fault repair".
•
Faulty control board, replace control
board.
•
Fan failure, replace fan.
•
Worn fan bearings, replace fan.
•
The fan blades scrape other objects,
check for interference with the fan
blades by cables etc.
•
The fan fixing bolts are loose, retighten
the fan fixing bolts.
2
Refrigeratio-
n system
failure
Does not cool and
reports a cooling
fault.
•
No power on (standby), check the main
power switch and check the operating
display screen that it is switched on.
•
Loose circuit connections, tighten circuit
connectors.
•
Circuit open or short circuit, check the
circuit open or short circuit and repair
the mains supply.
•
Inverter failure, replace the inverter.
•
Damaged control board, replace control
board.
•
Faulty
compressor
motor,
replace
compressor.
Operation & Maintenance Instruction