User Manual
86
Parameter
Explanation
Range
2-Time
Grid over-voltage 2 (V>>) tripping time
0–600 s
Min-V prot.
Under-voltage protection
1-V
min
Grid under-voltage 1 (V<)
46 V–230 V
1-Time
Grid under-voltage 1 (V<) tripping time
0–600 s
2-V
min
Grid under–voltage 2 (V<<)
46 V–230 V
2-Time
Grid under–voltage 2 (V<<) tripping time
0–600 s
Max-F prot.
Over-frequency protection
1-F
max
Grid over-frequency 1 (F>)
50.00 Hz–55.00 Hz
1-Time
Grid over-frequency 1 (F>) tripping time
0–600 s
2-F
max
Grid over-frequency 2 (F>>)
50.00 Hz–55.00 Hz
2-Time
Grid over-frequency 2 (F>>) tripping time
0–600 s
Min-F prot.
Under-frequency protection
1-F
min
Grid under-frequency 1 (F<)
45.00 Hz–50.00 Hz
1-Time
Grid under-frequency 1 (F<) tripping time
0–600 s
2-F
min
Grid under-frequency 2 (F<<)
45.00 Hz–50.00 Hz
2-Time
Grid under-frequency 2 (F<<) tripping
time
0–600 s
10.7
Viewing the Error Codes
Viewing Active Error
For the
!
icon or the “Error” state on the
main screen,
press
to view the current
faults. Refer to section
5.2
in the SH5K-20
quick user manual for error description and
troubleshooting.
Error Active P1/1
001 GRID 008
Code
Type
Refer to the following table for error type explanations.
Error Type
Explanation
GRID
Grid faults (AC side)
PV
PV faults (DC side)
SYS
System errors (inverter)
PER
Permanent faults
WARN
Warnings
BDCF
Faults of battery charge/discharge circuit
BDCPF
Permanent faults of battery charge/discharge circuit
BATW
Battery warnings
BATP
Battery protection
BATF1
Battery faults
BATF2