User Manual
51
6.8.1 Connecting the Power Cable
A fuse with the specification of 150 V/125 A (type: Bussmann BS88 125LET) is
integrated to the
BAT-
terminal.
A two-pole DC circuit breaker with over-current protection (voltage
rating not less than 100 V and current rating not less than 100 A)
should be installed between the inverter and the battery.
Cable Requirements
Cross-section: 16 mm
2
–
25 mm
2
, OT25-6, cable diameter: 13 mm–16 mm.
Procedure:
1.
Remove the battery cable
jacket.
15 mm
2.
Crimp the OT terminal and
install the heat shrinkable
casing, as shown below.
3.
Unscrew the swivel nut from
the
BAT+
and
BAT-
ports.
4.
Lead the cable through the
cable gland.