User Manual
38
E
L = E + (2~3)mm
1
2
1: Heat shrink tubing
2
:
OT/DT terminal
2.
Remove the screw on the grounding terminal and fasten the cable with a
screwdriver.
A
B
C
Item
Description
Specification
A
Cable socket
Not included in the delivery scope.
B
Screw
M5
×
12 mm (3.0 N
m)
C
Grounding
cable
The second PE conductor should be of the same
cross-sectional area as the original PE conductor in the
AC connector. The cable is not included in the delivery
scope.
3.
Apply paint to the grounding terminal to ensure corrosion resistance.