User Manual
52
5.
Loosen
and remove the
screw sets on the BAT+ and
BAT- terminal blocks.
6.
Fasten the cables to the
corresponding terminals
(torque 2.5 N
m).
Be sure to adhere to the following
screw assembly sequence: screw
head, spring washer, fender washer,
OT terminal.
-
-
7.
Fasten the swivel nut with a torque of 5 N
m–6 N
m and connect the
other end to the battery
6.8.2 Connecting the CAN Cable
The CAN cable enables the communication between the inverter and the Li-ion
battery from LG, Sungrow, GCL, Pylon (US2000B), BYD or TAWAKI.
Procedure:
1.
Take out the CAN cable
(terminal marks CANH and
CANL) from the packaging.
2.
Unscrew the swivel nut from
any
Com.
port.
3.
Lead the cable through the
cable gland.