10.4.2 Setting the EPS Function
The reserved capacity is the on-grid minimum battery discharge level. The
reserved battery capacity will be supplied to the emergency loads in the off-grid
system.
EPS Setting
Enable
Disable
Reserved Capacity
EPS Setting
000 %
Must install an
EPS box if the EPS
function is enabled!
If the battery type is set to “Other Battery”, it is not need to set the reserved
capacity.
If the EPS function is enabled, the buzzer inside the inverter will beep
intermittently for 20 s when the battery level is lower than the threshold value
specified in the following table.
Tab. 10-2
Threshold Values of Different Batteries
Battery Type
SOC Threshold
Sungrow (retrofitting system) / LG
≤ 6 %
BYD
≤ 11 %
GCL
≤ 16 %
Pylon (US2000B), TAWAKI
≤ 21 %
Lead-acid
≤ 45 V