User Manual
95
Parameter
Explanation
Default
Range
Q4 Ref.
Reactive power
at voltage V4
-030.0
%
-030.0 %
-030.0 %
Leading Q
/Sn
Lagging Q
/Sn
200
Grid voltage, V
Q/Sn
V2
V3
V4
210
220
230
240
250
260
270
20%
30%
10%
20%
30%
10%
0%
V1
Fig. 12-2
Reactive Power Regulation Curve in Q(u) Curve (“AU” for example)
12.3
Active Power Response
The submenu is as shown on the right.
Refer to “
” for the navigation.
Press
/ to select the desired option and
Press
ENT
to confirm.
Active Power
Volt-watt
Frq-watt
Volt-watt (Chrg)
12.3.1 Volt-watt Response
The Volt-watt response mode is enabled by default. Set four grid voltages. The
output power of the inverter will vary in response to the grid voltages.
Volt-watt
Enable
Disable
1/2
V1 Ref.
207.0V
V2 Ref.
220.0V
V3 Ref.
250.0V
V4 Ref.
265.0V
P1 Ref.
100.0%
P2 Ref.
100.0%
P3 Ref.
100.0%
P4 Ref.
020.0%
Tab. 12-4
“
Volt-Watt
” Mode Parameter Explanations
Parameter
Explanation
Default
Range
AU
NZ
V1 Ref.
Grid voltage
reference value 1
207.0 V
207.0 V
46 V–299 V
V2 Ref.
Grid voltage
reference value 2
220.0 V
220.0 V