Chapter 5
Replacing Chassis Components
5-17
FIGURE 5-15
Reconnecting the Alarm Board Cables
4. Route the cables into the cable guides.
5. Consider your next step:
■
If you installed the alarm board as part of another procedure, return to that
procedure.
■
Otherwise, perform the following tasks to bring the server back online:
■
Section 6.1.1, “Installing the PCI Mezzanine” on page 6-1
■
Section 6.1.2, “Installing the Top Cover” on page 6-3
■
Section 6.1.3, “Removing Antistatic Measures” on page 6-4
■
Section 6.1.4, “Reinstalling the Server Chassis in the Rack” on page 6-5
■
Section 6.1.5, “Reconnecting Cables to the Server” on page 6-7
■
Section 6.1.6, “Powering On the Server” on page 6-8
5.7
Replacing the LED Board
5.7.1
Removing the LED Board
1. Prepare the server for LED board removal. See:
■
Section 2.3.1, “Powering Off the Server” on page 2-3