Chapter 5
Replacing Chassis Components
5-9
FIGURE 5-8
Installing the System Fan Assembly Into the Chassis
4. Route the fan assembly cable back into the cable guides.
5. Consider your next step:
■
If you installed the fan assembly as part of another procedure, return to that
procedure.
■
Otherwise, perform the following tasks to bring the server back online:
■
Section 6.1.2, “Installing the Top Cover” on page 6-3
■
Section 6.1.3, “Removing Antistatic Measures” on page 6-4
■
Section 6.1.4, “Reinstalling the Server Chassis in the Rack” on page 6-5
■
Section 6.1.5, “Reconnecting Cables to the Server” on page 6-7
■
Section 6.1.6, “Powering On the Server” on page 6-8
5.4
Replacing the Hard Drive Fan Assembly
(FT1)
The hard drive fan assembly is labeled FT1.
Содержание Netra T5220
Страница 1: ...Sun Netra T5220 Server Service Manual Part No E21359 02 January 2012...
Страница 14: ...1 4 Sun Netra T5220 Server Service Manual January 2012 FIGURE 1 1 Diagnostic Flowchart...
Страница 39: ...Chapter 1 Server Diagnostics 1 29 FIGURE 1 8 Flowchart of ALOM CMT CLI Variables for POST Configuration...
Страница 156: ...5 26 Sun Netra T5220 Server Service Manual January 2012...
Страница 171: ...Appendix A Signal Pinouts A 7...
Страница 172: ...A 8 Sun Netra T5220 Server Service Manual January 2012...