4-10
Sun Netra T5220 Server Service Manual • January 2012
2. With the PCI mezzanine installed and cabled, loosen the appropriate card
securing screws (
FIGURE 4-3
).
3. Remove the replacement card from its packaging and place it onto an antistatic
mat.
4. If a filler panel is installed, remove it by pulling the tab (
FIGURE 4-7
).
5. Lower the card into position on the PCI mezzanine, then slide it to the right to
seat it into the connector (
FIGURE 4-7
).
6. Tighten the appropriate card securing screws and PCI retainers (
FIGURE 4-7
).
FIGURE 4-7
Installing the PCI-X 3 Card in the PCI Mezzanine
7. Bring the server back online. See
Section 4.1, “Powering Off and Powering On
the Server” on page 4-1
.