compressor. As a standard, superheat is factory set
at 12-15°F and should not need adjustment. The
superheat temperature is monitored and controlled by
the auxiliary control module (EVD Driver) mounted on
the door of the electric box. It is recommended that
STULZ Product Support be contacted if adjustment is
required.
CAUTION
Do not exceed 20°F superheat. Exceeding
this temperature may cause failure of the
compressor.
2.11.4 Hot Gas Bypass
A electronic hot gas bypass system is provided for
freeze protection and capacity control. The auxiliary
control module (EVD Driver) mounted on the door
of the electric box manages operation of the hot
gas valve. The hot gas regulator valve allows
refrigerant to fl ow from the discharge line directly
to the evaporator through an auxiliary connection
downstream of the thermal expansion valve. This
is used to maintain the evaporator at a minimum
constant pressure as the heating load varies.
The hot gas (discharge) regulating valve is set to
prevent the surface temperature of the evaporator
coil from dropping below 35°F. The bypass
temperature is factory set and no adjustment should
be necessary. It is recommended that STULZ
Product Support be contacted if adjustment is
required.
2-19
2.11.5 EC Fans
The speed of the EC fans are controlled via a 0
to 10 VDC signal from the system controller. The
controller is pre-set by the factory for the correct
fan speed confi guration and should not require
adjustment. If it is determined that the air fl ow needs
adjustment, this may be done using the controller’s
programming menu selections. Refer to Section
4.4.4
for instructions on adjusting airfl ow using the
system controller. It is recommended that STULZ
Product Support be contacted when initially making
adjustments to the controller.