STULZ CyberRow DX Series Installation, Operation & Maintenance Manual
4-19
4.5.3.4
Alarm Screen Messages
ALARM MESSAGE
DESCRIPTION OF ALARM CONDITION
High Temperature
Air temperature is above user defi ned alarm setpoint.
Low Temperature
Air temperature is below user defi ned alarm setpoint.
High Humidity
Humidity is above user defi ned alarm setpoint
Low Humidity
Humidity is below user defi ned alarm setpoint.
Sensor Failure
Sensor is disconnected or faulty. (The failed sensor is identifi ed.)
Communication Failure
External and/or internal communication lost (BMS or pLAN)
Condensate Pan Full
Water level in condensate pan is reaching an unsafe level.
Moisture
Water sensed by any combination of a leak detector or condensate
pan level switch.
Fan Failure
Upper, Middle and/or Lower fan failure.
Change Filter
Filter replacement time interval elapsed; fi lter needs to be replaced.
No Air Flow
Insuffi cient airfl ow per air proving switch.
Smoke/Fire
An alarm condition detected by the smoke detector or fi restat.
Optional Temp High Alarm
Temperature is above alarm threshold (user confi gurable).
Optional Temp Low Alarm
Temperature is below alarm threshold (user confi gurable).
High Head Pressure
Head Pressure is above user confi gured alarm threshold.
Low Suction Pressure
Suction Pressure is below user confi gured alarm threshold.
EVD Driver Offl ine
EEV & EHGB control driver error.