STULZ CyberRow DX Series Installation, Operation & Maintenance Manual
4-48
4.9.5 Sensor Failure Packed Bit Variables
Bit
Sensor Failures 1
Sensor Failures 2
0
Middle temperature
Reserved
1
Upper temperature
Reserved
2
Lower temperature
Reserved
3
Return temperature
Reserved
4
Return humidity
Reserved
5
Static air pressure
Reserved
6
Suction pressure
Reserved
7
Suction temperature
Reserved
8
Discharge pressure
Reserved
9
Discharge temperature
Reserved
10
Remote temperature
Reserved
11
Remote humidity
Reserved
12
Entering water temperature
Reserved
13
Leaving water temperature
Reserved
14
Reserved
Reserved
15
Reserved
Reserved
4.9.6 Digital Input Packed Bit Variables
Bit
Digital Inputs 1
Digital Inputs 2
0
Remote shutdown
Customer alarm 2
1
Customer alarm 1
Customer alarm 3
2
Water
Reserved
3
Condensate pan
Reserved
4
Humidifi er
Reserved
5
Moisture
Reserved
6
Middle fan alarm
Reserved
7
Upper fan alarm
Reserved
8
Fire/smoke
Reserved
9
Lower fan alarm
Reserved
10
Dual power input A
Reserved
11
Dual power input B
Reserved
12
Circuit 1 low pressure
Reserved
13
Circuit 1 high pressure
Reserved
14
Pump alarm
Reserved
15
Humidifi er lockout
Reserved