STULZ CyberRow DX Series Installation, Operation & Maintenance Manual
Information
Menu
4-16
(Continued on next page)
Setpoint Values
Temperature: 72°F
Humidity:
45%
Control:
Standard
Dehumidify rh: 52.3
Humidify DP:
46.4
Press ( ) or ( ) Key
4.5.2.7 Setpoint
Values
Displays the current operating Temperature and Humidity setpoints and control
method. If confi gured for Dewpoint control, the controller displays the calculated
dewpoint setpoints for dehumidifi cation and humidifi cation as derived from the
operating temperature and humidity setpoints.
(Continued from previous page)
Screen Lock Feature
You may lock any of the status display screens, bypassing the display screen
time-out function. This is sometimes useful to maintain visibility to a specifi c
screen when testing, making adjustments or troubleshooting the system.
Simultaneously press the program
(Prg)
and Enter (
)
key for
approximately 3 seconds to turn the screen lock feature On or Off. When a
screen is locked it remains displayed unless you press the Up ( ) or Down
(
) arrow keys to select a different screen within the menu loop. A symbol ( )
appears in the upper right corner indicating the screen lock feature is On.
Discharge Pressure
000psi
4.5.2.6 Discharge Pressure
The Discharge Pressure status screen only appears if your unit is a water or water/
glycol cooled DX system. It displays the current operating head pressure. Discharge
pressure is managed by the system controller based on the input of the head
pressure transducer.
Press ( ) or ( ) Key
4.5.2.8 Compressor Status
Displays the status icon (On or Off) for the system compressor and shows the
status of the High Pressure and Low Pressure switches (Open or Closed). It also
shows the current status (On or Off) of the compressor and indicates "
Min O
n"
if the compressor minimum off time has elapsed. If the minimum off time has
not elapsed, the display will show "
Min O
ff" and the actual minimum off time will
appear next to it.
Press ( ) or ( ) Key
Compressor 1 Status
LP:C
HP:C
Status:
Off
Min On
4.5.2.9 EEV
Status
Displays the current operating position of the electronic expansion valve. The
current suction pressure and temperature and the superheat temperature appear
below. The bar gauge next to the valve icon provides a visual representation of
the output signal controlling the valve position.
Press ( ) or ( ) Key
EEV Status
Pos: 50.0%
Suc
P 0.0
T 0.0
SH
0.0
4.5.2.5
Remote Supply Temperature/Humidity Sensor
The remote temperature and humidity screens appear if your unit is
confi gured for a remote supply T/H sensor. The screens display the supply air
temperature and humidity as measured by the sensor which is to be customer
installed in the cold aisle. Remote dewpoint is calculated by the controller
based on the remote supply T/H sensor inputs and shown at the bottom of the
display screen. Values measured by the sensor may be used to control the
temperature and humidity.
Press ( ) or ( ) Key
Rem Suppl Hum Sensor
00%rh
Remote dewpoint 00.0°F
Press ( ) or ( ) Key
Rem Suppl Temp Sensor
00.0°F