background image

SIME Brakes

13/05/16

M10054-02-A

Installation and maintenance

SIDEOS Box 2

4/17

Non contractual photographs.

Instructions of this manual must be adhered to, to obtain the performance and the safety of operation of the equipment.

Encoder and limit switch 51 questionnaire 

No. Q01390-01

Dimensions limit switch 51  

 

No.  T10003-01

Installation and maintenance SIDEOS One 

No. M10054-01

Limit switch 51 - Stromag 

 

Catalog 

No.          D142

 

Installation and maintenance  No. 151-00004

 

EMC 

No. 900-00001

2 - OUTPUTS CONTACTS USE

2-1 Use of overspeed outputs

Triggering  of  the  secured  contacts  outputs  :  Overspeed  C4 

(terminals  :  25-26)  and  C5  (terminals  :  27-28),  indicates  an 

emergency  situation  and  must  drive,  directly  or  via  a  safety 

relay,  the  redundant  contactors  of  the  safety  brakes  supply 

(mechanical stop of type 0). 
See diagram examples on chapter : 4.
The information output : Overspeed C6 (terminals : 29-30) can 

be used to give triggering information signal to the customer 

PLC, the stop control being processed otherwise via the secured 

Overspeed contacts.

2-2 Use of System Fault outputs 

Triggering of the secured outputs : System fault C1 (terminals: 

19-20) and C2 (terminals : 21-22), indicates an operation fault 

of the monitoring system : 
Those signals must be processed in order to maintain the ma-

chinery in a safe state.

 

>

Mechanical stop (stop of type 0): the secured contacts out-

puts must drive directly or via a safety relay the redundant 

contactors of the service brakes supply.

 

>

Electrical stop (stop of type 1) : the secured contacts out-

puts must drive the electrical stop of the hoidting motion, the 

customer PLC giving back the signal that the System Fault 

information is taken into account by 2 loops feedbacks.

See diagram examples on chapter : 4.
The information output System Fault C3 (terminals : 23-24) can 

be used to give the triggering information signal to the customer 

PLC, the stop control being processed otherwise via the secured 

Overspeed contacts.

Restart

 :

As indicated in the diagram examples in ch.4, restart of SIDEOS 

Box 2 (reset) must not restart the installation, but only allows  

the restart of the machinery from a control position with good 

visibility of the hazardous area.

Periodical checking

 :

When activation of 

SIDEOS Box 2

 outputs is not frequent (hois-

ting normal application), a procedure of switching off / switching 

on of the 

SIDEOS Box 2 

must be defined by the integrator of 

the SIDEOS One system, to carry out periodically the automatic 

and global TEST of the 

SIDEOS box 2

 unit.

3 - INPUTS CONTACTS CHARACTERISTICS

 

>

Ascent order

 (terminals 13-14)

Ascent contact is closed during a hoisting Ascent working order.

 

>

Descent order

 (terminals 15-16)

Descent contact is closed during a hoisting Descent working 

order.

 

>

High Speed order

 (terminals 17-18)

High Speed contact is closed during a hoisting High Speed 

working order.

ATTENTION !

The High Speed connection cable is imperatively 

shielded to avoid the risk of short-circuit in the 

connection cable.

Otherwise,  connect  the  High  Speed  contact 

between terminals 15 and 18,  and  this contact 

must imperatively be open (Low Speed order) 

when a Hoisting Stop order is present (Ascent 

and Descent order absent).

 

>

Loop feedback : System Fault

 (terminals 31-32 + 33-34)

 -Output  contacts  C1  and  C2  are  used  to  drive  directly  

2 internal relays of the customer PLC, which contacts drive 

a mechanical stop through the service brakes or an electri-

cal stop through the controller.

 -A NC contact of each of these relays is inserted in the res-

pective System Fault feedback loop. Those contacts must 

imperatively close, when the contacts C1 and C2 open, to 

indicate a System Fault. This allows to the 

SIDEOS Box 

2

 to check the opening of the associated relays and the 

customer PLC taking into account.

Reminder of EN ISO 13849-2 standard

 :

Short-circuits between conductors are excluded in an elec-

trical  enclosure  (enclosure  and  connection  must  comply 

with the requirements of CEI/EN 60204-1standard).

 -If this exclusion is not possible, it will then be necessary to 

include a contact indicating the service brakes closing or 

the electrical stop in each feedback loop.

 -In case of C1 and C2 contacts use in an input loop of a 

safety relay, those loop feedbacks can be shunted.

ATTENTION

 !

In this case, taking into account of the System 

Fault  triggering by the customer PLC and  pos-

sible short-circuits in the connection cables of C1 

and C2 contacts are no more controlled by the  

SIDEOS box 2

 unit.

The customer will make sure that all these faults 

will be detected by its system (for example : sa-

fety relay with input loops control).
The  achieved  performance  level  will  then  de-

pend on the performance level achieved by the 

safety relay.

SIME Brakes

 

www.stromag.com  -  

Customer service / Tel. : +33(0)1 49 90 32 20 / Fax : +33(0)1 49 89 06 38

Содержание SIDEOS Box 2

Страница 1: ...and maintenance M10054 02 SIDEOS Box 2 Adapted to interfaces up to PL e CATEGORY 4 according to ISO IEC 13849 1 SPEED MONITORING UNIT SIME Brakes www stromag com Customer service Tel 33 0 1 49 90 32 2...

Страница 2: ...4 2 2 Use of System Fault outputs 4 3 INPUTS CONTACTS CHARACTERISTICS 5 4 EXAMPLES OF APPLICATIONS 6 4 1 OVERSPEED mechanical stop SYSTEM FAULT electrical stop 6 4 2 OVERSPEED mechanical stop via safe...

Страница 3: ...1 NOTES AND SYMBOLS According to EC regulations we use facing some paragraphs symbols defining hazards and informing the user about the consequences of not following the instructions of this installa...

Страница 4: ...and the taking into account by the customer PLC It allows to obtain when installation is correct a speed moni toring system secured up to the category 4 with the perfor mance level of PL e according t...

Страница 5: ...ion a procedure of switching off switching on of the SIDEOS Box 2 must be defined by the integrator of the SIDEOS One system to carry out periodically the automatic and global TEST of the SIDEOS box 2...

Страница 6: ...tors triggering and possible short circuits in the connection cables of C4 and C5 contacts are no more controlled by the SIDEOS box 2 unit The customer will make sure that all these faults will be det...

Страница 7: ...econditioning SYSTEM FAULT System Fault secured contacts outputs C1 and C2 drive directly two redundant relays K1 and K2 of the customer PLC they are inserted on the hoisting control line and control...

Страница 8: ...op A NC contact of K1 and K2 relays is inserted in the respec tive feedback loop to check that the System Fault is taken into account by the customer PLC If a feedback loop remains open during a Syste...

Страница 9: ...voltage Breaking capacity Maxi AC15 500VA 230VAC DC13 50W Breaking capacity Mini 50mW 5V 2mA The maximum current flowing in the contacts will be limited by a fuse 2A Using an arc suppressing device a...

Страница 10: ...vent of fault 37 38 POWER ON Loop feedback System Fault Loop feedback System Fault Loop feedback Loop feedback Overspeed Descent Overspeed OV linked to ground Consistency control RLS3 RLS4 Ascent or D...

Страница 11: ...upply voltage range 10 30V Push pull output with inverted signals Maxi no load consumption 160mA Standard shielded cable 0 25 to 0 5mm The cable ways and connection should respect the safety EMC regul...

Страница 12: ...urope BP24 18150 La Guerche L Aubois FRANCE SIDEOS Box2 Indice B Stromag GKN LANDS SYSTEM Power on H1 H2 H3 Overspeed fault System Screw M8x10 nut HU8 washers 6 INSTALLATION PARAMETERS SETTING 6 1 Par...

Страница 13: ...ominal speed to the stop VS Necessary number of encoder pulses to confirm the overspeed output triggering SP1 0 SP2 Hoisting Low Speed detected by encoder N 1 10 rpm Hoisting Low Speed detected by enc...

Страница 14: ...G OF 3 SPEED THRESHOLDS Step Point to check Command Possible fault Causes 1 Normal operation and accordance of the speed read on the LCD display with the required speed HS High Speed speed active make...

Страница 15: ...ng if parameter setting Reverse the parameter setting CW CCW After each test restore the SIDEOS One in its previous configuration make a RESTART and proceed with the following test 8 DIAGNOSIS The fol...

Страница 16: ...ult Encoder coupling fault Check the encoder coupling mini speed during operation at speed 2 or speed 3 0 2Hz encoder Modification of the parameter setting of the variable speed drive Speed contact fa...

Страница 17: ...otection and connection of mains input Mounting and connection of the encoder Speed contact Connection of the feedback loop NC contact Periodic test ACTION OF THE OUTPUT CONTACTS TOWARDS Alarm Electri...

Страница 18: ...nnections parame ters of the others components of the control chain such as the frequency converter the controller It is important to check that the assumptions used for the se lection stated in the c...

Страница 19: ...32 20 T l France 33 0 1 49 90 32 22 Fax 33 0 1 49 89 06 38 E mail sales gkn com PRODUCTION CENTER AFTER SALES DEPARTMENT Avenue de l Europe BP 24 18150 La Guerche sur l Aubois France T l 33 0 2 48 80...

Отзывы: