Instructions of this manual must be adhered to, to obtain the performance and the safety of operation of the equipment.

Encoder and limit switch 51 questionnaire 

No. Q01390-01

Dimensions limit switch 51  

 

No.  T10003-01

Installation and maintenance SIDEOS One 

No. M10054-01

Limit switch 51 - Stromag 

 

Catalog 

No.          D142

 

Installation and maintenance  No. 151-00004

 

EMC 

No. 900-00001

è

 Check of triggering and reaction mode of the PLC for each SIDEOS One :

SIDEOS function

 SIDEOS modification

Hoisting 

control 

Action expected from the customer

System Fault

Disconnect a wire on the encoder input

Make hoisting 

operate to the 

nominal speed 

Check that the customer PLC  

reaction is in conformity 

for ex :  

closing of the emergency brakes.

Overspeed

Decrease the active parameter SPx

Differential speed 

if parameter setting 

Disconnect the wire A on the encoder input 

of the other SIDEOS One

Static slipping

Disconnect the Descent command and

make hoisting operate in Descent mode.

Dynamic slipping 

if parameter setting

Reverse the parameter-setting CW / CCW

After each test restore the 

SIDEOS One

 in its previous configuration, make a RESTART and proceed with the following test.

8 - DIAGNOSIS

The  following  indicators  provide  access  to  diagnosis  information 

for a quick troubleshooting of your application :

LED lights and LCD display are placed on the front of the 

SIDEOS 

One

When the correct voltage is applied, the LEDs POWER ON light up.
When a 

SIDEOS One

 makes an Autotest :

- The LED TEST flashes Orange.

Contacts C1-C2-C3-C4-C5-C6 are open.

- The LCD display indicates Autotest.
When a 

SIDEOS One

 validated its Autotest :

- The LED TEST lights up in green.

Contacts C1-C2-C3-C4-C5-C6 are closed

.

- The  LCD  display  indicates  the  active  speed  parameter  and  its 

value.

When a Test Fault occurs :

- The LED TEST lights up in red.

Contacts C1-C2-C3-C4-C5-C6 remain open.

- The LCD display indicates a Autotest Fault
When a System Fault occurs :

- The LED SYSTEM FAULT lights up.

Contacts C1-C2-C3 open

- The LCD display indicates the Fault which caused the triggering.
When an Overspeed occurs :

- The LED OVERSPEED lights up.

Contacts C4-C5-C6 open

- The LCD display indicates the Overspeed type which caused the 

triggering.

SIME Brakes

 

www.stromag.com  -  

Customer service / Tel. : +33(0)1 49 90 32 20 / Fax : +33(0)1 49 89 06 38

Содержание SIDEOS Box 2

Страница 1: ...and maintenance M10054 02 SIDEOS Box 2 Adapted to interfaces up to PL e CATEGORY 4 according to ISO IEC 13849 1 SPEED MONITORING UNIT SIME Brakes www stromag com Customer service Tel 33 0 1 49 90 32 2...

Страница 2: ...4 2 2 Use of System Fault outputs 4 3 INPUTS CONTACTS CHARACTERISTICS 5 4 EXAMPLES OF APPLICATIONS 6 4 1 OVERSPEED mechanical stop SYSTEM FAULT electrical stop 6 4 2 OVERSPEED mechanical stop via safe...

Страница 3: ...1 NOTES AND SYMBOLS According to EC regulations we use facing some paragraphs symbols defining hazards and informing the user about the consequences of not following the instructions of this installa...

Страница 4: ...and the taking into account by the customer PLC It allows to obtain when installation is correct a speed moni toring system secured up to the category 4 with the perfor mance level of PL e according t...

Страница 5: ...ion a procedure of switching off switching on of the SIDEOS Box 2 must be defined by the integrator of the SIDEOS One system to carry out periodically the automatic and global TEST of the SIDEOS box 2...

Страница 6: ...tors triggering and possible short circuits in the connection cables of C4 and C5 contacts are no more controlled by the SIDEOS box 2 unit The customer will make sure that all these faults will be det...

Страница 7: ...econditioning SYSTEM FAULT System Fault secured contacts outputs C1 and C2 drive directly two redundant relays K1 and K2 of the customer PLC they are inserted on the hoisting control line and control...

Страница 8: ...op A NC contact of K1 and K2 relays is inserted in the respec tive feedback loop to check that the System Fault is taken into account by the customer PLC If a feedback loop remains open during a Syste...

Страница 9: ...voltage Breaking capacity Maxi AC15 500VA 230VAC DC13 50W Breaking capacity Mini 50mW 5V 2mA The maximum current flowing in the contacts will be limited by a fuse 2A Using an arc suppressing device a...

Страница 10: ...vent of fault 37 38 POWER ON Loop feedback System Fault Loop feedback System Fault Loop feedback Loop feedback Overspeed Descent Overspeed OV linked to ground Consistency control RLS3 RLS4 Ascent or D...

Страница 11: ...upply voltage range 10 30V Push pull output with inverted signals Maxi no load consumption 160mA Standard shielded cable 0 25 to 0 5mm The cable ways and connection should respect the safety EMC regul...

Страница 12: ...urope BP24 18150 La Guerche L Aubois FRANCE SIDEOS Box2 Indice B Stromag GKN LANDS SYSTEM Power on H1 H2 H3 Overspeed fault System Screw M8x10 nut HU8 washers 6 INSTALLATION PARAMETERS SETTING 6 1 Par...

Страница 13: ...ominal speed to the stop VS Necessary number of encoder pulses to confirm the overspeed output triggering SP1 0 SP2 Hoisting Low Speed detected by encoder N 1 10 rpm Hoisting Low Speed detected by enc...

Страница 14: ...G OF 3 SPEED THRESHOLDS Step Point to check Command Possible fault Causes 1 Normal operation and accordance of the speed read on the LCD display with the required speed HS High Speed speed active make...

Страница 15: ...ng if parameter setting Reverse the parameter setting CW CCW After each test restore the SIDEOS One in its previous configuration make a RESTART and proceed with the following test 8 DIAGNOSIS The fol...

Страница 16: ...ult Encoder coupling fault Check the encoder coupling mini speed during operation at speed 2 or speed 3 0 2Hz encoder Modification of the parameter setting of the variable speed drive Speed contact fa...

Страница 17: ...otection and connection of mains input Mounting and connection of the encoder Speed contact Connection of the feedback loop NC contact Periodic test ACTION OF THE OUTPUT CONTACTS TOWARDS Alarm Electri...

Страница 18: ...nnections parame ters of the others components of the control chain such as the frequency converter the controller It is important to check that the assumptions used for the se lection stated in the c...

Страница 19: ...32 20 T l France 33 0 1 49 90 32 22 Fax 33 0 1 49 89 06 38 E mail sales gkn com PRODUCTION CENTER AFTER SALES DEPARTMENT Avenue de l Europe BP 24 18150 La Guerche sur l Aubois France T l 33 0 2 48 80...

Отзывы: