Instructions of this manual must be adhered to, to obtain the performance and the safety of operation of the equipment.
Encoder and limit switch 51 questionnaire
No. Q01390-01
Dimensions limit switch 51
No. T10003-01
Installation and maintenance SIDEOS One
No. M10054-01
Limit switch 51 - Stromag
Catalog
No. D142
Installation and maintenance No. 151-00004
EMC
No. 900-00001
è
Check of triggering and reaction mode of the PLC for each SIDEOS One :
SIDEOS function
SIDEOS modification
Hoisting
control
Action expected from the customer
System Fault
Disconnect a wire on the encoder input
Make hoisting
operate to the
nominal speed
Check that the customer PLC
reaction is in conformity
for ex :
closing of the emergency brakes.
Overspeed
Decrease the active parameter SPx
Differential speed
if parameter setting
Disconnect the wire A on the encoder input
of the other SIDEOS One
Static slipping
Disconnect the Descent command and
make hoisting operate in Descent mode.
Dynamic slipping
if parameter setting
Reverse the parameter-setting CW / CCW
After each test restore the
SIDEOS One
in its previous configuration, make a RESTART and proceed with the following test.
8 - DIAGNOSIS
The following indicators provide access to diagnosis information
for a quick troubleshooting of your application :
LED lights and LCD display are placed on the front of the
SIDEOS
One
When the correct voltage is applied, the LEDs POWER ON light up.
When a
SIDEOS One
makes an Autotest :
- The LED TEST flashes Orange.
-
Contacts C1-C2-C3-C4-C5-C6 are open.
- The LCD display indicates Autotest.
When a
SIDEOS One
validated its Autotest :
- The LED TEST lights up in green.
-
Contacts C1-C2-C3-C4-C5-C6 are closed
.
- The LCD display indicates the active speed parameter and its
value.
When a Test Fault occurs :
- The LED TEST lights up in red.
-
Contacts C1-C2-C3-C4-C5-C6 remain open.
- The LCD display indicates a Autotest Fault
When a System Fault occurs :
- The LED SYSTEM FAULT lights up.
-
Contacts C1-C2-C3 open
- The LCD display indicates the Fault which caused the triggering.
When an Overspeed occurs :
- The LED OVERSPEED lights up.
-
Contacts C4-C5-C6 open
- The LCD display indicates the Overspeed type which caused the
triggering.