MISTAKES OF INSTALLATION OR APPLICATION
:
Light off
Å
Å
Å
:
Light on
LCD
display
POWER
ON
TEST SYSTEM
OVER-
SPEED
Mistake types
Possible causes
Solutions
no 24VDC
supply on
terminals 2
and 3 of the
SIDEOS One
Lack of mains voltage
Check the wiring, the mains voltage
and correct the fault.
Restart the
SIDEOS One
.
Mains Protection Triggering :
Fuse F2- F3 out of order
Internal supply failure
Return the
SIDEOS One
for repair
Encoder 1 Fault
Å
/
Å
Å
Encoder
supply
short-circuit
External fault of wiring : Short-circuit
1of terminal UB to ground (OV)
Check the wiring and correct the fault.
Restart the
SIDEOS One
.
Encoder internal fault
Replace the encoder
Encoder 2 Fault
Å
/
Å
Å
Encoder
signals fault
External fault of wiring : Short-circuit -
cut wire - wire wrongly connected on
terminals 9 to 14
Check the wiring and correct the fault.
Restart the
SIDEOS One.
Encoder internal fault
Replace the encoder
Encoder 3 Fault
Å
/
Å
Å
Encoder
rotation fault
Encoder coupling fault
Check the encoder coupling
mini speed during operation at speed 2
or speed 3 < 0.2Hz (encoder)
Modification of the parameter-setting of
the variable speed drive
Speed
contact fault
Å
/
Å
Å
Wrong speed
information
Control fault
Ascent and Descent information
overlap
High Speed order in stop position.
Discrepancy of relays RLS3/RLS4 or
RLS5/RLS6
Relays RL1-RL2-RL3 or RL4 stuck
Check the wiring
Check the relays operation
Correct the fault.
Restart the
SIDEOS One
.
Contactor fault
Å
/
Å
Å
/
Å
Mistake in a
feedback loop
During a triggering System Fault or
Overspeed, the feedback loop remains
open
Check the feedback loops wiring
Check the wiring of KDS (4-5).
Check the relays :
RLS7-8-9-10-11-12-13-14
Restart the
SIDEOS One
.
Autotest fault
Å
Å
Å
Å
During the test or a reset demand, the
feedback loop remains open
Overspeed 2 (Low
Speed)
Overspeed 3 (High
Speed)
Diff speed
Static Slipping
Dynamic slipping
Å
/
Å
Å
Overspeed
Real Overspeed, see procedure of
start-up to know the causes of wrong
detection.
Check the parameter-setting
Check the encoder mounting
Check the variable speed drive
After carrying out all the indicated checkings, restart the SIDEOS One, if the fault persists consult us.
SIDEOS One INTERNAL FAULT
Internal fault
Å
/
Å
Å
Internal
signals fault
Overspeed function internal fault
Restart and check the programming of
the
SIDEOS One.
If the fault comes back, return the
SIDEOS One
for repair
Autotest fault
Å
Å
Å
Å
Internal
signals fault
Welding, short-circuit, faulty internal
component.