background image

SIME Brakes

13/05/16

M10054-02-A

Installation and maintenance

SIDEOS Box 2

15/17

Non contractual photographs.

Instructions of this manual must be adhered to, to obtain the performance and the safety of operation of the equipment.

Encoder and limit switch 51 questionnaire 

No. Q01390-01

Dimensions limit switch 51  

 

No.  T10003-01

Installation and maintenance SIDEOS One 

No. M10054-01

Limit switch 51 - Stromag 

 

Catalog 

No.          D142

 

Installation and maintenance  No. 151-00004

 

EMC 

No. 900-00001

MISTAKES OF INSTALLATION OR APPLICATION

       

   

 : 

Light off

      

Å

Å

Å

 : 

Light on

LCD 

display

POWER 

ON

TEST SYSTEM

OVER- 

SPEED

Mistake types

Possible causes

Solutions









no 24VDC 

supply on  

terminals 2 

and 3 of the 

SIDEOS One

Lack of mains voltage

Check the wiring, the mains voltage 

and correct the fault. 

Restart the 

SIDEOS One

.

Mains Protection Triggering :

 

Fuse F2- F3 out of order

Internal supply failure

Return the 

SIDEOS One

 for repair

Encoder 1 Fault

Å



/

Å

Å



Encoder 

supply 

short-circuit

External fault of wiring : Short-circuit 

1of terminal UB to ground (OV) 

Check the wiring and correct the fault. 

Restart the 

SIDEOS One

.

Encoder internal fault

Replace the encoder

Encoder 2 Fault

Å



/

Å

Å



Encoder 

signals fault

External fault of wiring : Short-circuit  - 

cut wire - wire wrongly connected on 

terminals 9 to 14

Check the wiring and correct the fault. 

Restart the 

SIDEOS One.

Encoder internal fault

Replace the encoder

Encoder 3 Fault

Å



/

Å

Å



Encoder 

rotation fault

Encoder coupling fault

Check the encoder coupling

mini speed during operation at speed 2 

or speed 3 <  0.2Hz (encoder)

Modification of the parameter-setting of 

the variable speed drive

Speed  

contact fault

Å



/

Å

Å



Wrong speed 

information

Control fault 
Ascent and Descent information 

overlap 
High Speed order in stop position.
Discrepancy of relays RLS3/RLS4 or 

RLS5/RLS6
Relays RL1-RL2-RL3 or RL4 stuck

Check the wiring 

Check the relays operation

Correct the fault. 

Restart the 

SIDEOS One

.

 Contactor fault

Å



/

Å

Å



/

Å

Mistake in a 

feedback loop 

During a triggering System Fault or 

Overspeed, the feedback loop remains 

open

Check the feedback loops wiring 

Check the wiring of KDS (4-5). 

Check the relays : 

RLS7-8-9-10-11-12-13-14

Restart the 

SIDEOS One

.

Autotest fault

Å

Å

Å

Å

During the test or a reset demand, the 

feedback loop remains open

Overspeed 2 (Low 

Speed)

Overspeed 3 (High 

Speed)

Diff speed 

Static Slipping

Dynamic slipping

Å



/

Å



Å

Overspeed

Real Overspeed, see procedure of 

start-up to know the causes of wrong 

detection.

Check the parameter-setting  

Check the encoder mounting   

Check the variable speed drive

After carrying out all the indicated checkings, restart the SIDEOS One, if the fault persists consult us.

SIDEOS One INTERNAL FAULT

Internal fault 

Å



/

Å

Å



Internal 

signals fault

Overspeed function internal fault

Restart and check the programming of 

the 

SIDEOS One.

 

If the fault comes back, return the 

SIDEOS One

 for repair

Autotest fault 

Å

Å

Å

Å

Internal 

signals fault

Welding, short-circuit, faulty internal 

component.

For each SIDEOS One :

SIME Brakes

 

www.stromag.com  -  

Customer service / Tel. : +33(0)1 49 90 32 20 / Fax : +33(0)1 49 89 06 38

Содержание SIDEOS Box 2

Страница 1: ...and maintenance M10054 02 SIDEOS Box 2 Adapted to interfaces up to PL e CATEGORY 4 according to ISO IEC 13849 1 SPEED MONITORING UNIT SIME Brakes www stromag com Customer service Tel 33 0 1 49 90 32 2...

Страница 2: ...4 2 2 Use of System Fault outputs 4 3 INPUTS CONTACTS CHARACTERISTICS 5 4 EXAMPLES OF APPLICATIONS 6 4 1 OVERSPEED mechanical stop SYSTEM FAULT electrical stop 6 4 2 OVERSPEED mechanical stop via safe...

Страница 3: ...1 NOTES AND SYMBOLS According to EC regulations we use facing some paragraphs symbols defining hazards and informing the user about the consequences of not following the instructions of this installa...

Страница 4: ...and the taking into account by the customer PLC It allows to obtain when installation is correct a speed moni toring system secured up to the category 4 with the perfor mance level of PL e according t...

Страница 5: ...ion a procedure of switching off switching on of the SIDEOS Box 2 must be defined by the integrator of the SIDEOS One system to carry out periodically the automatic and global TEST of the SIDEOS box 2...

Страница 6: ...tors triggering and possible short circuits in the connection cables of C4 and C5 contacts are no more controlled by the SIDEOS box 2 unit The customer will make sure that all these faults will be det...

Страница 7: ...econditioning SYSTEM FAULT System Fault secured contacts outputs C1 and C2 drive directly two redundant relays K1 and K2 of the customer PLC they are inserted on the hoisting control line and control...

Страница 8: ...op A NC contact of K1 and K2 relays is inserted in the respec tive feedback loop to check that the System Fault is taken into account by the customer PLC If a feedback loop remains open during a Syste...

Страница 9: ...voltage Breaking capacity Maxi AC15 500VA 230VAC DC13 50W Breaking capacity Mini 50mW 5V 2mA The maximum current flowing in the contacts will be limited by a fuse 2A Using an arc suppressing device a...

Страница 10: ...vent of fault 37 38 POWER ON Loop feedback System Fault Loop feedback System Fault Loop feedback Loop feedback Overspeed Descent Overspeed OV linked to ground Consistency control RLS3 RLS4 Ascent or D...

Страница 11: ...upply voltage range 10 30V Push pull output with inverted signals Maxi no load consumption 160mA Standard shielded cable 0 25 to 0 5mm The cable ways and connection should respect the safety EMC regul...

Страница 12: ...urope BP24 18150 La Guerche L Aubois FRANCE SIDEOS Box2 Indice B Stromag GKN LANDS SYSTEM Power on H1 H2 H3 Overspeed fault System Screw M8x10 nut HU8 washers 6 INSTALLATION PARAMETERS SETTING 6 1 Par...

Страница 13: ...ominal speed to the stop VS Necessary number of encoder pulses to confirm the overspeed output triggering SP1 0 SP2 Hoisting Low Speed detected by encoder N 1 10 rpm Hoisting Low Speed detected by enc...

Страница 14: ...G OF 3 SPEED THRESHOLDS Step Point to check Command Possible fault Causes 1 Normal operation and accordance of the speed read on the LCD display with the required speed HS High Speed speed active make...

Страница 15: ...ng if parameter setting Reverse the parameter setting CW CCW After each test restore the SIDEOS One in its previous configuration make a RESTART and proceed with the following test 8 DIAGNOSIS The fol...

Страница 16: ...ult Encoder coupling fault Check the encoder coupling mini speed during operation at speed 2 or speed 3 0 2Hz encoder Modification of the parameter setting of the variable speed drive Speed contact fa...

Страница 17: ...otection and connection of mains input Mounting and connection of the encoder Speed contact Connection of the feedback loop NC contact Periodic test ACTION OF THE OUTPUT CONTACTS TOWARDS Alarm Electri...

Страница 18: ...nnections parame ters of the others components of the control chain such as the frequency converter the controller It is important to check that the assumptions used for the se lection stated in the c...

Страница 19: ...32 20 T l France 33 0 1 49 90 32 22 Fax 33 0 1 49 89 06 38 E mail sales gkn com PRODUCTION CENTER AFTER SALES DEPARTMENT Avenue de l Europe BP 24 18150 La Guerche sur l Aubois France T l 33 0 2 48 80...

Отзывы: