6-2 Parameter-setting according to the selected function (Dynamic Slipping or Kinematic Linkage Breaking) 

      and mounting configuration :

SIDEOS N°1

SIDEOS N°2

Configuration

Encoder N°1

Encoder N°2

Kinematic linkage breaking

Kinematic linkage breaking

Drum

Drum

Drum

Motor

Kinematic linkage breaking

Dynamic Slipping

Drum

Motor

Dynamic Slipping

Dynamic Slipping

Drum

Drum

PARAMETERS

KINEMATIC LINKAGE BREAKING

DYNAMIC SLIPPING

Setting

Setting

VER

N/A

CL

French / English

NC

Pulses number / encoder N°1

Pulses number / encoder N°2

NS

Nominal speed detected by encoder N°1 in rpm

Nominal speed detected by encoder N°2 in rpm

DT

Deceleration time of the installation to pass from the nominal speed to the stop

VS

Necessary number of encoder pulses to confirm the overspeed output triggering

SP1

0

SP2

Hoisting Low Speed detected by encoder N°1 +10% (rpm)

Hoisting Low Speed detected by encoder N°2 +10% (rpm)

SP3

Hoisting High Speed detected by encoder N°1 +10% (rpm)

Hoisting High Speed detected by encoder N°2 +10% (rpm)

RC

Off : Inactive

Off : Inactive

DS

10 % 

0%

TS

Speed :  Input of a speed signal.

CW : Encoder rotation = clockwise

CCW : Encoder rotation = counter-clockwise

PARAMETERS

DETAILS FOR SETTING

NC

The selected encoder will deliver a frequency < 1000Hz at nominal speed otherwise the option of encoder frequency 

divider will be selected.

VS

The corresponding angle of the configured pulses number will be > mechanical clearance

The validation angle will be = VS x (360/NC) (Slipping).

The validation time will be = (60xVS) / (NC x Triggering speed)

SP2

Will be = SP3 if no hoisting Low Speed, KGV input will not be wired

RC

Will be set on ON if the 2 SIDEOS One monitor the Dynamic Slipping

The minimum speed allowed during a Start order will be > 0.2Hz at the encoder

DS

Setting of the maximum speed difference in % of the nominal speed (NS) 

for the Kinematic Linkage Breaking function 

CW/CCW

Rotation direction by watching the encoder axis from the front during the hoisting descent

SIME Brakes

 

www.stromag.com  -  

Customer service / Tel. : +33(0)1 49 90 32 20 / Fax : +33(0)1 49 89 06 38

Содержание SIDEOS Box 2

Страница 1: ...and maintenance M10054 02 SIDEOS Box 2 Adapted to interfaces up to PL e CATEGORY 4 according to ISO IEC 13849 1 SPEED MONITORING UNIT SIME Brakes www stromag com Customer service Tel 33 0 1 49 90 32 2...

Страница 2: ...4 2 2 Use of System Fault outputs 4 3 INPUTS CONTACTS CHARACTERISTICS 5 4 EXAMPLES OF APPLICATIONS 6 4 1 OVERSPEED mechanical stop SYSTEM FAULT electrical stop 6 4 2 OVERSPEED mechanical stop via safe...

Страница 3: ...1 NOTES AND SYMBOLS According to EC regulations we use facing some paragraphs symbols defining hazards and informing the user about the consequences of not following the instructions of this installa...

Страница 4: ...and the taking into account by the customer PLC It allows to obtain when installation is correct a speed moni toring system secured up to the category 4 with the perfor mance level of PL e according t...

Страница 5: ...ion a procedure of switching off switching on of the SIDEOS Box 2 must be defined by the integrator of the SIDEOS One system to carry out periodically the automatic and global TEST of the SIDEOS box 2...

Страница 6: ...tors triggering and possible short circuits in the connection cables of C4 and C5 contacts are no more controlled by the SIDEOS box 2 unit The customer will make sure that all these faults will be det...

Страница 7: ...econditioning SYSTEM FAULT System Fault secured contacts outputs C1 and C2 drive directly two redundant relays K1 and K2 of the customer PLC they are inserted on the hoisting control line and control...

Страница 8: ...op A NC contact of K1 and K2 relays is inserted in the respec tive feedback loop to check that the System Fault is taken into account by the customer PLC If a feedback loop remains open during a Syste...

Страница 9: ...voltage Breaking capacity Maxi AC15 500VA 230VAC DC13 50W Breaking capacity Mini 50mW 5V 2mA The maximum current flowing in the contacts will be limited by a fuse 2A Using an arc suppressing device a...

Страница 10: ...vent of fault 37 38 POWER ON Loop feedback System Fault Loop feedback System Fault Loop feedback Loop feedback Overspeed Descent Overspeed OV linked to ground Consistency control RLS3 RLS4 Ascent or D...

Страница 11: ...upply voltage range 10 30V Push pull output with inverted signals Maxi no load consumption 160mA Standard shielded cable 0 25 to 0 5mm The cable ways and connection should respect the safety EMC regul...

Страница 12: ...urope BP24 18150 La Guerche L Aubois FRANCE SIDEOS Box2 Indice B Stromag GKN LANDS SYSTEM Power on H1 H2 H3 Overspeed fault System Screw M8x10 nut HU8 washers 6 INSTALLATION PARAMETERS SETTING 6 1 Par...

Страница 13: ...ominal speed to the stop VS Necessary number of encoder pulses to confirm the overspeed output triggering SP1 0 SP2 Hoisting Low Speed detected by encoder N 1 10 rpm Hoisting Low Speed detected by enc...

Страница 14: ...G OF 3 SPEED THRESHOLDS Step Point to check Command Possible fault Causes 1 Normal operation and accordance of the speed read on the LCD display with the required speed HS High Speed speed active make...

Страница 15: ...ng if parameter setting Reverse the parameter setting CW CCW After each test restore the SIDEOS One in its previous configuration make a RESTART and proceed with the following test 8 DIAGNOSIS The fol...

Страница 16: ...ult Encoder coupling fault Check the encoder coupling mini speed during operation at speed 2 or speed 3 0 2Hz encoder Modification of the parameter setting of the variable speed drive Speed contact fa...

Страница 17: ...otection and connection of mains input Mounting and connection of the encoder Speed contact Connection of the feedback loop NC contact Periodic test ACTION OF THE OUTPUT CONTACTS TOWARDS Alarm Electri...

Страница 18: ...nnections parame ters of the others components of the control chain such as the frequency converter the controller It is important to check that the assumptions used for the se lection stated in the c...

Страница 19: ...32 20 T l France 33 0 1 49 90 32 22 Fax 33 0 1 49 89 06 38 E mail sales gkn com PRODUCTION CENTER AFTER SALES DEPARTMENT Avenue de l Europe BP 24 18150 La Guerche sur l Aubois France T l 33 0 2 48 80...

Отзывы: