background image

4.2  Detailed Description 

4.2.1  SOC (State Of Charge) Calculation 

With the help of a proprietary patented software algorithm, the System-Manager is capable to ”learn“ the 
characteristics and parameters of the battery. This SOC reading is very accurate and therefore is the 
basis for most controlling and monitoring functions. However, if system components are directly 
connected to the battery, the state of charge can only be determined with the help of the optional  current 
sensors HS200. The state of charge always refers to the actual capacity which the battery has in 
accordance to its age. So a SOC of 50 % does not mean that half of the battery’s nominal rated capacity 
can be used, but that only half of the battery’s REAL MEASURED capacity is remaining. 

The state of charge is not dependant on the battery voltage, but on the amount of energy taken out. 
Traditional controllers usually determine a final load voltage that hardly ever corresponds to the discharge 
depth. During discharge, nominal acid density is being reduced and sulphates are placed on the battery 
plates. If discharge is too deep, this growth leads to harmful sulphatation that reduces the battery’s 
capacity considerably, thus making the battery useless for energy storage. The traditional measuring 
procedures (Ah balancing, acid density measuring) are time-consuming and cost intensive and are 
seldom integrated in charge controllers. 

If generators or loads are directly connected to the battery without current sensor HS200, the SOC gets 
“tricked” and its determination is wrong. However, despite erroneously measured SOC values., the 
System-Manager still prevents the battery from falling below certain voltage values, in order to protect the 
battery from a too-deep damaging discharge 

The System-Manager is able to convert to a voltage regulation mode (chapter 6.5, page 13). Now 
System-Manager will operate like a conventional charge controller. We recommend this conversion when 
using additional generators (diesel, wind, etc.) or loads which are connected direct to the battery (inverter, 
etc.). See for option 2.2 current sensor HS200, too. 

4.2.2  Overcharge Protection 

The overcharge protection prevents uncontrolled gassing within the battery cells. The gas development is 
depending on the acid temperature and cell voltage. So the System-Manager monitors the ambient 
temperatures and adjusts the battery’s maximum allowed charge 
voltage. The overcharge protection and voltage limitation is 
independent on the battery’s state of charge, since the 
decomposition of electrolyte is exclusively depending on the voltage 
and the temperature. This means that charging is already limited 
even though the battery is not completely charged. 

Overcharging the battery leads to uncontrolled gassing. Here the 
electrolyte is decomposed into oxygen and hydrogen. The 
consequences are harmful oxidation processes and mechanical 
damages since the gas blisters may knock out active lead material 
from the lead plates.  

What is even worse is that the uncontrolled gassing in closed 
batteries e. g. sealed or fluid batteries where the gas pressure can 
even burst or crack the battery case. Frequent overcharging damages the battery casing. The charging 
process and the overcharge protection are thus regulated by a new hybrid System-Manager utilizing 
pulse width modulation in order to insure smooth battery charging. The user in particular should not 
choose a float voltage too high via user settings. If you want to program this value individually from the 
System-Manager’s factory setting, please take note of the battery manufacturers' recommendations. 

-20
-40

-10
-14

-0
32

10
50

20
68

30
86

40
104

50
122

2,20

2,25

2,30

2,35

2,40

2,45

2,50

2,55

2,60

13,2

13,5

13,8

14,1

14,4

14,7

15,0

15,3

15,6

equ

alis

atio

n S

OC

 < 4

0%

 

boo

st S

OC

 <7

0%

norm

al

°C

°F

4.2.3  Temperature Compensation Of Final Charge Voltage 

As the battery temperature increases, the acid/lead battery’s optimal final load voltage decreases. A 
constant final charge voltage leads to uncontrolled gassing in the case of higher battery temperatures, 
and undercharging in case of low temperatures. The temperature compensation software algorithm 
automatically decreases the final charge voltage at higher temperatures and increases them at lower 
ones. The temperature compensation system with the sensor integrated in the System-Manager 
influences all three overcharge thresholds. 

  The attached external battery temperature sensor should therefore be mounted next to the battery to 

determine the exact temperature. 

 

Содержание Power Tarom 2070

Страница 1: ...tion and Operation Instruction Manual System Manager for Photovoltaic systemes Power Tarom Tarom 2070 Tarom 2140 Tarom 4055 Tarom 4110 Tarom 4140 09 47 PHOTOVOLTAIK PHOTOVOLTAIC PHOTOVOLTAIQUE FOTOVOL...

Страница 2: ...ET CONFIGURATIONS 11 6 2 MAIN MENU 12 6 3 MENU MANU 12 6 4 MENU LOGG 13 6 5 MENU CONF 13 6 6 MENU PROG 14 6 7 EXAMPLE OF CONFIGURATION 17 6 8 EXAMPLE OF PROGRAMMING 18 7 INSTALLATION 18 7 1 PRECAUTION...

Страница 3: ...work Read the chapter Installation chapter 7 page 18 Make sure that all Precautions chapter 7 1 page 18 are taken Only start to install your System Manager when you are sure that you have understood a...

Страница 4: ...ected to this System Manager the user has to accept the consequences 2 Quick installation instructions Please do all steps following the numbers below Do not go ahead if any step failed 1 Check system...

Страница 5: ...t automatically registers the maximum permissible temperature and disconnect the loads in the case it is exceeded Now the complete radiating surface of the heat sink could be used for the power loss p...

Страница 6: ...ut parallel operation of System Managers As soon as the charge current of the main solar array connected directly to the System Manager is reduced to a minimum the second array will be disconnected fr...

Страница 7: ...he internal resistance of the battery itself are compensated automatically in the sophisticated patented software inside the System Manager without using extra sensor cables In order to protect the ba...

Страница 8: ...n prevents uncontrolled gassing within the battery cells The gas development is depending on the acid temperature and cell voltage So the System Manager monitors the ambient temperatures and adjusts t...

Страница 9: ...and can only then be programmed if the battery has been configured to be of liquid electrolyte type It is activated when the battery falls below a certain SOC status 4 2 7 Automatic Monthly Mixture O...

Страница 10: ...cates how much remaining capacity the battery still has The SOC is never 100 as due to technical reasons it is easier to indicate a two digit number U Bat Since the voltage drop between System Manager...

Страница 11: ...5 2 Alarm contact All PowerTaroms are equipped with a signal contact See illustration in chapter 6 4 to locate the terminals The signal relais switches if a system fault occurs under over voltage over...

Страница 12: ...nter the corresponding menu Other than this Main Menu the keys always have the normal functions described below to navigate through menus With the arrow keys you can scr parameters can be changed by t...

Страница 13: ...sing blocking diodes in the module cables In the System Manager there is a small data logger built in which can be used for a quick view of the energy allocation To conduct research where data of an e...

Страница 14: ...ated state of charge of the battery After entering this menu by pressing OK you may switch with the keys associated SOC in SOC 12V system 24V system 48V system 0 10 9 V 21 8V 43 6V 10 10 90 10 99V 21...

Страница 15: ...charge should be activated After having entered the window by pressing OK the first line shows Boost___voltage and you may alter the voltage appearing in the second line by pressing the arrow keys By...

Страница 16: ...disconnectio System Manager allows only these values for disconnect an difference of 0 8V 12V 1 6V 24V und 3 2 disconnection you must first increase Possibilities for programming by voltage r The char...

Страница 17: ...ogram the acid density and the equalizing charging equal charging When the configuration is set to these windows are not activated Battery Typ By pressing any one of the 4 keys under the cover you lea...

Страница 18: ...ow keys to avoid changing the values Hint If you have programmed a wrong value you will again reach the window with the undesired value by pressing the OK key a few times When you have reached the win...

Страница 19: ...ust be out of children s and unauthorized persons reach The basis on which controller is to be installed should not be easily flammable During operation the backside of the controller cooling body hea...

Страница 20: ...ndispensable to install a safety fuse directly on the battery pole This fuse sec For isolated systems it is not necessary not common or even not permitted by national laws to ground connect the compon...

Страница 21: ...ation of safety fuses Finally secure all cables within the controller s immediate surrounding by strain relieves All other components must also be strain relieved 7 5 Uninstalling Uninstall the regula...

Страница 22: ...bviously Even a discharge between clouds or a strike far can induce energy pulses into the elec conducting parts of the installation like wires structure or electronic components Not even a visible an...

Страница 23: ...GND GND GND lay grounding cables separately to the DC cables Inside protection zone protected photovoltaic field Outside protection zone unprotected photovoltaic field avoid loops between module cabl...

Страница 24: ...in and out the battery are calculated and displayed at this PowerTarom and his TarCom logger You only need one HS200 for the whole system Currents higher than the maximum of 200A will not layed but d...

Страница 25: ...2x M40 14 28mm 4x M32 12 21mm 1x M25 17mm t 12 2 le glands and t sink PowerTarom 2140 4110 and 4140 4x M40 14 28mm 2x M32 wo heat sinks 1mm 1x M25 8 17mm Weight 9 k 10 kg 9 kg 10 kg g 10kg Dimensions...

Страница 26: ...s the three left keys ok together to reset the display Module current The module current exceeds the max currents allowed Although this will not cause a defect The solar generator exceeds the nominal...

Страница 27: ...ties unprofessional installation or commissioning incorrect or negligent handling improper transport excessive loading use of improper equipment faulty construction work unsuitable construction locati...

Страница 28: ......

Отзывы: