6.8  Example Of Programming 

This example shows how pre-
set configurations can be 
altered within the main menu 
item “PROG”. Changes are 
displayed in black letters. 

First of all, open the cover of 
the System-Manager, and 
press any key. The Main Menu 
with the four submenus will 
appear in the display. Please 
press the key below the 
corresponding submenu title 
(MANU, LOGG, CONF, 
PROG). In this example, press the very rightmost key under PROG. Note that this key has the function 
“return to Main menu” in all other windows. 

After having pressed this key, the topmost item of the PROG menu “end of charge” appears. Since we 

es the expression equal voltage and you may change the 

 

 

 for confirmation and the original window for equal charging appears.  

are not concerned with this item, we scroll past this window and move to the window boost charging by 
pressing the UP arrow key 

. Once we reach the desired item “equal charging”, then press the OK key to 

activate the window.  The first line indicat
voltage value (here 15V) to 15.3 by pressing the arrow keys. By pressing OK, this value is stored, and at
the same time the expression equal time now appears in the first line. Now you can adjust the time that
the increased equalizing charge voltage should be maintained by pressing the arrow keys 

▲▼

 (here: 

from 02:00 to 03:00). Press OK

Hint:  If you want to make sure that you have programmed correctly, press only OK and move through all 

Equal Charging submenu items to check the values.  Do not press the arrow keys to avoid changing 
the values. 

Hint:  If you have programmed a wrong value, you will again reach the window with the undesired value 

by pressing the OK key a few times. When you have reached the window with the error, change the 
value to the correct one by pressing the arrow keys

▲▼

7  Installation 

7.1  Precautions 

Do not install any PV or electronic components in rooms where flamm

Within the battery’s immediate surroundings, explosive gases may be generated. So please see that the
battery room is adequately ventilated and avoid generating sparks. 

able gas mixtu

 

res may occur! 

The following instructions for batteries must be adhered. We recommend these basic precautions for 
any country.  Check your local electric and safety codes for all applicable precautions in dealing with 

DC wiring and battery installations. 

ainst exp

 8. P cau

e) and 9.

ti

 DIN (German) VDE 0510 part 2, sections: 7. Precautions ag

against risks occurring by electrolyte gas (hydrogen sulphid

losio

 Loca

danger,

on 

re

tions 

 National Electric Code including article No. 690. The unit shall be installed 

according to this regulation 

20

0m

20

0

m

m

7.2  Location Of Installation 

The System-Manager must be connected to the solar PV array, the battery and the 
loads. The line loss and drops in voltage should be kept to a minimum, so the 
System-Manager must be installed in a way that the shortest cable possible and 
the most direct access can be used. This is a major decisive factor for the battery’s 
location as well as for the solar PV array’s location. The cable lengths to the loads 
have a lesser effect on System-Manager site selection since distribution throughout 
the building or site is necessary. 

m

 

18 

Содержание Power Tarom 2070

Страница 1: ...tion and Operation Instruction Manual System Manager for Photovoltaic systemes Power Tarom Tarom 2070 Tarom 2140 Tarom 4055 Tarom 4110 Tarom 4140 09 47 PHOTOVOLTAIK PHOTOVOLTAIC PHOTOVOLTAIQUE FOTOVOL...

Страница 2: ...ET CONFIGURATIONS 11 6 2 MAIN MENU 12 6 3 MENU MANU 12 6 4 MENU LOGG 13 6 5 MENU CONF 13 6 6 MENU PROG 14 6 7 EXAMPLE OF CONFIGURATION 17 6 8 EXAMPLE OF PROGRAMMING 18 7 INSTALLATION 18 7 1 PRECAUTION...

Страница 3: ...work Read the chapter Installation chapter 7 page 18 Make sure that all Precautions chapter 7 1 page 18 are taken Only start to install your System Manager when you are sure that you have understood a...

Страница 4: ...ected to this System Manager the user has to accept the consequences 2 Quick installation instructions Please do all steps following the numbers below Do not go ahead if any step failed 1 Check system...

Страница 5: ...t automatically registers the maximum permissible temperature and disconnect the loads in the case it is exceeded Now the complete radiating surface of the heat sink could be used for the power loss p...

Страница 6: ...ut parallel operation of System Managers As soon as the charge current of the main solar array connected directly to the System Manager is reduced to a minimum the second array will be disconnected fr...

Страница 7: ...he internal resistance of the battery itself are compensated automatically in the sophisticated patented software inside the System Manager without using extra sensor cables In order to protect the ba...

Страница 8: ...n prevents uncontrolled gassing within the battery cells The gas development is depending on the acid temperature and cell voltage So the System Manager monitors the ambient temperatures and adjusts t...

Страница 9: ...and can only then be programmed if the battery has been configured to be of liquid electrolyte type It is activated when the battery falls below a certain SOC status 4 2 7 Automatic Monthly Mixture O...

Страница 10: ...cates how much remaining capacity the battery still has The SOC is never 100 as due to technical reasons it is easier to indicate a two digit number U Bat Since the voltage drop between System Manager...

Страница 11: ...5 2 Alarm contact All PowerTaroms are equipped with a signal contact See illustration in chapter 6 4 to locate the terminals The signal relais switches if a system fault occurs under over voltage over...

Страница 12: ...nter the corresponding menu Other than this Main Menu the keys always have the normal functions described below to navigate through menus With the arrow keys you can scr parameters can be changed by t...

Страница 13: ...sing blocking diodes in the module cables In the System Manager there is a small data logger built in which can be used for a quick view of the energy allocation To conduct research where data of an e...

Страница 14: ...ated state of charge of the battery After entering this menu by pressing OK you may switch with the keys associated SOC in SOC 12V system 24V system 48V system 0 10 9 V 21 8V 43 6V 10 10 90 10 99V 21...

Страница 15: ...charge should be activated After having entered the window by pressing OK the first line shows Boost___voltage and you may alter the voltage appearing in the second line by pressing the arrow keys By...

Страница 16: ...disconnectio System Manager allows only these values for disconnect an difference of 0 8V 12V 1 6V 24V und 3 2 disconnection you must first increase Possibilities for programming by voltage r The char...

Страница 17: ...ogram the acid density and the equalizing charging equal charging When the configuration is set to these windows are not activated Battery Typ By pressing any one of the 4 keys under the cover you lea...

Страница 18: ...ow keys to avoid changing the values Hint If you have programmed a wrong value you will again reach the window with the undesired value by pressing the OK key a few times When you have reached the win...

Страница 19: ...ust be out of children s and unauthorized persons reach The basis on which controller is to be installed should not be easily flammable During operation the backside of the controller cooling body hea...

Страница 20: ...ndispensable to install a safety fuse directly on the battery pole This fuse sec For isolated systems it is not necessary not common or even not permitted by national laws to ground connect the compon...

Страница 21: ...ation of safety fuses Finally secure all cables within the controller s immediate surrounding by strain relieves All other components must also be strain relieved 7 5 Uninstalling Uninstall the regula...

Страница 22: ...bviously Even a discharge between clouds or a strike far can induce energy pulses into the elec conducting parts of the installation like wires structure or electronic components Not even a visible an...

Страница 23: ...GND GND GND lay grounding cables separately to the DC cables Inside protection zone protected photovoltaic field Outside protection zone unprotected photovoltaic field avoid loops between module cabl...

Страница 24: ...in and out the battery are calculated and displayed at this PowerTarom and his TarCom logger You only need one HS200 for the whole system Currents higher than the maximum of 200A will not layed but d...

Страница 25: ...2x M40 14 28mm 4x M32 12 21mm 1x M25 17mm t 12 2 le glands and t sink PowerTarom 2140 4110 and 4140 4x M40 14 28mm 2x M32 wo heat sinks 1mm 1x M25 8 17mm Weight 9 k 10 kg 9 kg 10 kg g 10kg Dimensions...

Страница 26: ...s the three left keys ok together to reset the display Module current The module current exceeds the max currents allowed Although this will not cause a defect The solar generator exceeds the nominal...

Страница 27: ...ties unprofessional installation or commissioning incorrect or negligent handling improper transport excessive loading use of improper equipment faulty construction work unsuitable construction locati...