background image

8  Overvoltage protection in your photovoltaic system 

ve vo

Photovoltaic systems have to be mounted very often on sites like mountain tops or next to high structures 
like transmission poles.  These locations have a high risk of damages due to lightning. Harmful levels of 
over voltage will occur through direct hits or even more frequently induced by flashes as far as 100 
meters. To prevent your electronic equipment from these damaging over voltage spikes, you have to 
include all parts of your system into the over voltage protection: building, modules, frames, wires, 
controller, inverter, loads, antenna and grounding. 

In any case, a good lightning protection can reduce the risk of damages in a great measure, but not 
prevent them completely. We can give you some hints for further reading, but it is not possible to describe 
the overvoltage protection for all installations in detail here. 

See these sites for more recommendations for lightning protection 

http://www.iea-pvpsuk.org.uk/PV%20for%20standalone/T3-13%202003.pdf

O r  ltage can damage your PV system 

 

r check the internet sites from producers of over voltage protection units:  

ww.dehn.de

o

w

,  

www.phoenixcontact.de/ueberspannungsschutz

 ,  

www.citel.de

 , 

www.cirprotec.com

 , … 

Transient voltage spikes can be caused by effects of lightning. It’s not necessary that the system got a 
direct hit – in this case the energy is normally tha
that the degree of destruction is obviously.  

Even a discharge between clouds or a strike far 
can induce energy pulses into the elec
conducting parts of the installation like wires, 
structure or electronic components.  

Not even a visible and/or audible lightning strike
thunder can cause a transient voltage spike. 
discharges of electrostatic charge may cause tran
spikes of some 1000 V ! Such transient voltage  ike 
can be a positive or a negative pulse related to the ground. 

 

s induced by distant lightning 

 

 

Internal overvoltage protection 

 

 to 

se

rgy 

If the power is too 

 will be destroyed by 

the plus (+) pole of the 

ient 

e Power

g rack should be grounded. The module cables to the 

to be as short as possible 

r and modules should be as short as possible 

he modules (and the load) may not be separated to avoid loops between 

transient over voltage spikes  

t high 

away 

trical 

metal 

 with 

Also 

sient 

sp

High voltage spike

Inside the PowerTarom there are electronic 
components (varistors and suppressor diods)
limit the energy of transient spikes. The
elements normally absorb some limited ene
and convert them into heat. 

 

big even these elements
overheating.  

Some general hints for the over voltag
protection in your system: 

 

-

  grounding of 

battery helps to reduce the trans
voltage level. All plus (+) terminals of th

-

  the module frames and the mountin

regulator should have been shielded. 

-

  all connections to the ground have 

-

  the connections between regulato

-

  the + and – cable of t

Tarom regulator are internally connected. 

them 

solar

generator 

transient voltage spike

electronic

equipment

transient
voltage

clamped
voltage

M+

suppressor

varistors

diode

to
regulator

ground

 

22 

Содержание Power Tarom 2070

Страница 1: ...tion and Operation Instruction Manual System Manager for Photovoltaic systemes Power Tarom Tarom 2070 Tarom 2140 Tarom 4055 Tarom 4110 Tarom 4140 09 47 PHOTOVOLTAIK PHOTOVOLTAIC PHOTOVOLTAIQUE FOTOVOL...

Страница 2: ...ET CONFIGURATIONS 11 6 2 MAIN MENU 12 6 3 MENU MANU 12 6 4 MENU LOGG 13 6 5 MENU CONF 13 6 6 MENU PROG 14 6 7 EXAMPLE OF CONFIGURATION 17 6 8 EXAMPLE OF PROGRAMMING 18 7 INSTALLATION 18 7 1 PRECAUTION...

Страница 3: ...work Read the chapter Installation chapter 7 page 18 Make sure that all Precautions chapter 7 1 page 18 are taken Only start to install your System Manager when you are sure that you have understood a...

Страница 4: ...ected to this System Manager the user has to accept the consequences 2 Quick installation instructions Please do all steps following the numbers below Do not go ahead if any step failed 1 Check system...

Страница 5: ...t automatically registers the maximum permissible temperature and disconnect the loads in the case it is exceeded Now the complete radiating surface of the heat sink could be used for the power loss p...

Страница 6: ...ut parallel operation of System Managers As soon as the charge current of the main solar array connected directly to the System Manager is reduced to a minimum the second array will be disconnected fr...

Страница 7: ...he internal resistance of the battery itself are compensated automatically in the sophisticated patented software inside the System Manager without using extra sensor cables In order to protect the ba...

Страница 8: ...n prevents uncontrolled gassing within the battery cells The gas development is depending on the acid temperature and cell voltage So the System Manager monitors the ambient temperatures and adjusts t...

Страница 9: ...and can only then be programmed if the battery has been configured to be of liquid electrolyte type It is activated when the battery falls below a certain SOC status 4 2 7 Automatic Monthly Mixture O...

Страница 10: ...cates how much remaining capacity the battery still has The SOC is never 100 as due to technical reasons it is easier to indicate a two digit number U Bat Since the voltage drop between System Manager...

Страница 11: ...5 2 Alarm contact All PowerTaroms are equipped with a signal contact See illustration in chapter 6 4 to locate the terminals The signal relais switches if a system fault occurs under over voltage over...

Страница 12: ...nter the corresponding menu Other than this Main Menu the keys always have the normal functions described below to navigate through menus With the arrow keys you can scr parameters can be changed by t...

Страница 13: ...sing blocking diodes in the module cables In the System Manager there is a small data logger built in which can be used for a quick view of the energy allocation To conduct research where data of an e...

Страница 14: ...ated state of charge of the battery After entering this menu by pressing OK you may switch with the keys associated SOC in SOC 12V system 24V system 48V system 0 10 9 V 21 8V 43 6V 10 10 90 10 99V 21...

Страница 15: ...charge should be activated After having entered the window by pressing OK the first line shows Boost___voltage and you may alter the voltage appearing in the second line by pressing the arrow keys By...

Страница 16: ...disconnectio System Manager allows only these values for disconnect an difference of 0 8V 12V 1 6V 24V und 3 2 disconnection you must first increase Possibilities for programming by voltage r The char...

Страница 17: ...ogram the acid density and the equalizing charging equal charging When the configuration is set to these windows are not activated Battery Typ By pressing any one of the 4 keys under the cover you lea...

Страница 18: ...ow keys to avoid changing the values Hint If you have programmed a wrong value you will again reach the window with the undesired value by pressing the OK key a few times When you have reached the win...

Страница 19: ...ust be out of children s and unauthorized persons reach The basis on which controller is to be installed should not be easily flammable During operation the backside of the controller cooling body hea...

Страница 20: ...ndispensable to install a safety fuse directly on the battery pole This fuse sec For isolated systems it is not necessary not common or even not permitted by national laws to ground connect the compon...

Страница 21: ...ation of safety fuses Finally secure all cables within the controller s immediate surrounding by strain relieves All other components must also be strain relieved 7 5 Uninstalling Uninstall the regula...

Страница 22: ...bviously Even a discharge between clouds or a strike far can induce energy pulses into the elec conducting parts of the installation like wires structure or electronic components Not even a visible an...

Страница 23: ...GND GND GND lay grounding cables separately to the DC cables Inside protection zone protected photovoltaic field Outside protection zone unprotected photovoltaic field avoid loops between module cabl...

Страница 24: ...in and out the battery are calculated and displayed at this PowerTarom and his TarCom logger You only need one HS200 for the whole system Currents higher than the maximum of 200A will not layed but d...

Страница 25: ...2x M40 14 28mm 4x M32 12 21mm 1x M25 17mm t 12 2 le glands and t sink PowerTarom 2140 4110 and 4140 4x M40 14 28mm 2x M32 wo heat sinks 1mm 1x M25 8 17mm Weight 9 k 10 kg 9 kg 10 kg g 10kg Dimensions...

Страница 26: ...s the three left keys ok together to reset the display Module current The module current exceeds the max currents allowed Although this will not cause a defect The solar generator exceeds the nominal...

Страница 27: ...ties unprofessional installation or commissioning incorrect or negligent handling improper transport excessive loading use of improper equipment faulty construction work unsuitable construction locati...

Страница 28: ......

Отзывы: