background image

Before this menu function is activated, it is necessary to disconnect the solar PV 

re 

ears, 

 If 

 to 

G

ot be 

are usable, and in Day and Week data 

 

 

 

display from today’s current running data 

arrow key 

n be linked to this system as an additional option. See Options (chapter 3.2, page 

t always shows the Ah which have flowed into the System-Manager and the 

f battery energy in percentage of capacity afterwards (SOC). The energy which has 

s, 

This window shows the accumulated values of energy in and out of the system since the 

s

Within this menu
changes and als

modules and all loads. Before Uninstalling (chapter 7.5, page 21) please refer to the 
related information. After having scrolled to this window, a self test can be started by 

pressing OK. The System-Manager examines its performance components: software and parts of the 
hardware. When the window appears “TEST MODUL OK; TEST LOAD OK“, the operation and hardwa
have been verified to be in good condition. If ”TEST MODUL FAIL“ and/or "TEST LOAD FAIL" app
re-start the Test again after you have verified that the modules and loads were properly disconnected.
the failure message appears again, disconnect all connections and please return the System-Manager
your authorized dealer. 

6.4  Menu LOG  

Within this menu, you can recall stored data values. Within the following menu windows, values cann
changed. Therefore, only the arrow keys 

▲▼

 and the MENU key 

displays, the OK key toggles from Current Day or Week values, to the values stored in history for the 

weeks. These accounting is only done if the PowerTarom can detect the “night” 

condition each day. This is not possible by using blocking diodes in the module cables.   
In the System-Manager, there is a small data logger built in which can be used for a quick view of the 
energy allocation. To conduct research where data of an exact value is required, we recommend you 
purchase the optional data logger (chapter 

previous days or

3.2, page 5) 

Within this window, the rest of the available capacity is indicated as per the System-
Manager’s SOC calculation in ampere hour units, when the nominal capacity of the 

battery is entered under the Menu CONF(chapter 6.5, page 13 ). 

From this menu window, you can read the actual daily value of amp-hours in and out of
the System-Manager. Press OK to toggle the 

values to the stored data values for the last 7 days. You can choose the desired day to view with the 

▲▼

. ”day“ simply stands for today and “day 1“ for the day before, “day 2” means two days ago. 

When a new day of logging starts, the data for each of “day” to “day6” will be shifted to the previous day, 
i.e. the 7

th

 day data will be replaced with the data for the 6

th

 day, 6

th

 day replaced by 5

th

 day, etc. An 

external data logger ca
5). The daily readou
remaining amount o
flowed out of the System-Manager is shown on the second line.

 

Similarly, the weekly value indicated by “week“  shows the accumulated Ah value from the last 7 week
battery SOC, as well as energy spent (OUT) during the week. 

day of installation, plus battery in the upper right corner. You can reset all these values 

tallation. Please use the key sequence described in Installation and operation to reset 

this window’s values. 

6.5  Menu CONF 

during a new in

, you can configure your system components. Here you can review all programming 

o activate pre-set configurations. Within this menu, the type of battery has to be set. 

Please find detailed information on programming the type of battery in 

 

 

13

Содержание Power Tarom 2070

Страница 1: ...tion and Operation Instruction Manual System Manager for Photovoltaic systemes Power Tarom Tarom 2070 Tarom 2140 Tarom 4055 Tarom 4110 Tarom 4140 09 47 PHOTOVOLTAIK PHOTOVOLTAIC PHOTOVOLTAIQUE FOTOVOL...

Страница 2: ...ET CONFIGURATIONS 11 6 2 MAIN MENU 12 6 3 MENU MANU 12 6 4 MENU LOGG 13 6 5 MENU CONF 13 6 6 MENU PROG 14 6 7 EXAMPLE OF CONFIGURATION 17 6 8 EXAMPLE OF PROGRAMMING 18 7 INSTALLATION 18 7 1 PRECAUTION...

Страница 3: ...work Read the chapter Installation chapter 7 page 18 Make sure that all Precautions chapter 7 1 page 18 are taken Only start to install your System Manager when you are sure that you have understood a...

Страница 4: ...ected to this System Manager the user has to accept the consequences 2 Quick installation instructions Please do all steps following the numbers below Do not go ahead if any step failed 1 Check system...

Страница 5: ...t automatically registers the maximum permissible temperature and disconnect the loads in the case it is exceeded Now the complete radiating surface of the heat sink could be used for the power loss p...

Страница 6: ...ut parallel operation of System Managers As soon as the charge current of the main solar array connected directly to the System Manager is reduced to a minimum the second array will be disconnected fr...

Страница 7: ...he internal resistance of the battery itself are compensated automatically in the sophisticated patented software inside the System Manager without using extra sensor cables In order to protect the ba...

Страница 8: ...n prevents uncontrolled gassing within the battery cells The gas development is depending on the acid temperature and cell voltage So the System Manager monitors the ambient temperatures and adjusts t...

Страница 9: ...and can only then be programmed if the battery has been configured to be of liquid electrolyte type It is activated when the battery falls below a certain SOC status 4 2 7 Automatic Monthly Mixture O...

Страница 10: ...cates how much remaining capacity the battery still has The SOC is never 100 as due to technical reasons it is easier to indicate a two digit number U Bat Since the voltage drop between System Manager...

Страница 11: ...5 2 Alarm contact All PowerTaroms are equipped with a signal contact See illustration in chapter 6 4 to locate the terminals The signal relais switches if a system fault occurs under over voltage over...

Страница 12: ...nter the corresponding menu Other than this Main Menu the keys always have the normal functions described below to navigate through menus With the arrow keys you can scr parameters can be changed by t...

Страница 13: ...sing blocking diodes in the module cables In the System Manager there is a small data logger built in which can be used for a quick view of the energy allocation To conduct research where data of an e...

Страница 14: ...ated state of charge of the battery After entering this menu by pressing OK you may switch with the keys associated SOC in SOC 12V system 24V system 48V system 0 10 9 V 21 8V 43 6V 10 10 90 10 99V 21...

Страница 15: ...charge should be activated After having entered the window by pressing OK the first line shows Boost___voltage and you may alter the voltage appearing in the second line by pressing the arrow keys By...

Страница 16: ...disconnectio System Manager allows only these values for disconnect an difference of 0 8V 12V 1 6V 24V und 3 2 disconnection you must first increase Possibilities for programming by voltage r The char...

Страница 17: ...ogram the acid density and the equalizing charging equal charging When the configuration is set to these windows are not activated Battery Typ By pressing any one of the 4 keys under the cover you lea...

Страница 18: ...ow keys to avoid changing the values Hint If you have programmed a wrong value you will again reach the window with the undesired value by pressing the OK key a few times When you have reached the win...

Страница 19: ...ust be out of children s and unauthorized persons reach The basis on which controller is to be installed should not be easily flammable During operation the backside of the controller cooling body hea...

Страница 20: ...ndispensable to install a safety fuse directly on the battery pole This fuse sec For isolated systems it is not necessary not common or even not permitted by national laws to ground connect the compon...

Страница 21: ...ation of safety fuses Finally secure all cables within the controller s immediate surrounding by strain relieves All other components must also be strain relieved 7 5 Uninstalling Uninstall the regula...

Страница 22: ...bviously Even a discharge between clouds or a strike far can induce energy pulses into the elec conducting parts of the installation like wires structure or electronic components Not even a visible an...

Страница 23: ...GND GND GND lay grounding cables separately to the DC cables Inside protection zone protected photovoltaic field Outside protection zone unprotected photovoltaic field avoid loops between module cabl...

Страница 24: ...in and out the battery are calculated and displayed at this PowerTarom and his TarCom logger You only need one HS200 for the whole system Currents higher than the maximum of 200A will not layed but d...

Страница 25: ...2x M40 14 28mm 4x M32 12 21mm 1x M25 17mm t 12 2 le glands and t sink PowerTarom 2140 4110 and 4140 4x M40 14 28mm 2x M32 wo heat sinks 1mm 1x M25 8 17mm Weight 9 k 10 kg 9 kg 10 kg g 10kg Dimensions...

Страница 26: ...s the three left keys ok together to reset the display Module current The module current exceeds the max currents allowed Although this will not cause a defect The solar generator exceeds the nominal...

Страница 27: ...ties unprofessional installation or commissioning incorrect or negligent handling improper transport excessive loading use of improper equipment faulty construction work unsuitable construction locati...

Страница 28: ......

Отзывы: