trouble shooting 

ad 6.) LC-Display not working: battery fuse ok? cabling ok? polarity ok? check battery voltage at A+ and 
A

terminal ? display plug loose?  Press the three left buttons 

 

 ok simultaneously to restart the display.  

ad 7)  no module current: polarity ok? module connection ok (parallel/serial)? check module voltage 
outside the PowerTarom? solar radiation high enough?  

ad 8.)  load not working: “deep protection” active ? polarity ok? load fuses ok? 

If you do not have external module switches you have to connect the battery first and then the module 
input to support the automatic voltage identification in 12/24V systems. 

 

3  Application range 

The system controller can be used in PV energy supplies with battery storage within the field of  business 
and commerce as well as in firms and telecommunication devices.  

Although the case is IP65  waterproofed it should be protected against heavy rain or direct sun.  
In order to keep the voltage drop between controller and battery to a minimum please use only short 
battery cables. 
To adapt the final charge voltage of the battery for optimal charging the attached temperature sensor 
should be mounted next to the battery clamps. 

The controller should only be used for regulating solar modules. It regulates the charging current from the 
modules using the shunt (short circuit) principle. However, the battery can also be charged by multiple 
PowerTaroms or other sources with appropriate battery charge functions. 

3.1  Power range 

The controller can be used in a wide range of performance and 
temperature. It automatically registers the maximum permissible 
temperature and disconnect the loads in the case it is exceeded. 
Now the complete radiating surface of the heat sink could be 
used for the power loss produced during charging.  

20°C

50°C

20

0

40

100

120

20

40

100

120

Load current

%

M

od

ul

cu

rr

e

nt

Select dimensioning in a way that the ambient temperature line is 
not exceeded in the case of maximal charge and discharge 
currents. With an ambient temperature of 20 °C and correct 
installation the controller can process both module and load 
nominal currents (see labels). These nominal currents 
correspond to 100 % in the diagram. 

3.2  Options 

The System-Manager can be operated with the following additional devices which you can purchase at 
authorized dealers. The options of description and instructions are pointed out by following listed 
possibilities and examples of use: 

 External current sensors can be installed in the power 

wires of generators or loads that are not being controlled 
by the System-Manager directly. This enables the 
System-Manager to calculate the state of charge (SOC) 
even when external sources like wind or diesel 
generators charge the battery, or when bigger loads like 
inverters are connected directly to the battery. The 
shunts register the current and send the current readings 
into the System-Manager digitally. 

G

AC

DC

AC

DC

Data

transmission

  The pair-shunt solution enables separate measurement and indication of charging and 

discharging currents. All load and charging currents have to be conducted across either the 

charge or discharge current measuring shunt, except for those currents already flowing through the 
System-Manager (the System-Manager already measures these currents internally automatically).  

 

 

5

Содержание Power Tarom 2070

Страница 1: ...tion and Operation Instruction Manual System Manager for Photovoltaic systemes Power Tarom Tarom 2070 Tarom 2140 Tarom 4055 Tarom 4110 Tarom 4140 09 47 PHOTOVOLTAIK PHOTOVOLTAIC PHOTOVOLTAIQUE FOTOVOL...

Страница 2: ...ET CONFIGURATIONS 11 6 2 MAIN MENU 12 6 3 MENU MANU 12 6 4 MENU LOGG 13 6 5 MENU CONF 13 6 6 MENU PROG 14 6 7 EXAMPLE OF CONFIGURATION 17 6 8 EXAMPLE OF PROGRAMMING 18 7 INSTALLATION 18 7 1 PRECAUTION...

Страница 3: ...work Read the chapter Installation chapter 7 page 18 Make sure that all Precautions chapter 7 1 page 18 are taken Only start to install your System Manager when you are sure that you have understood a...

Страница 4: ...ected to this System Manager the user has to accept the consequences 2 Quick installation instructions Please do all steps following the numbers below Do not go ahead if any step failed 1 Check system...

Страница 5: ...t automatically registers the maximum permissible temperature and disconnect the loads in the case it is exceeded Now the complete radiating surface of the heat sink could be used for the power loss p...

Страница 6: ...ut parallel operation of System Managers As soon as the charge current of the main solar array connected directly to the System Manager is reduced to a minimum the second array will be disconnected fr...

Страница 7: ...he internal resistance of the battery itself are compensated automatically in the sophisticated patented software inside the System Manager without using extra sensor cables In order to protect the ba...

Страница 8: ...n prevents uncontrolled gassing within the battery cells The gas development is depending on the acid temperature and cell voltage So the System Manager monitors the ambient temperatures and adjusts t...

Страница 9: ...and can only then be programmed if the battery has been configured to be of liquid electrolyte type It is activated when the battery falls below a certain SOC status 4 2 7 Automatic Monthly Mixture O...

Страница 10: ...cates how much remaining capacity the battery still has The SOC is never 100 as due to technical reasons it is easier to indicate a two digit number U Bat Since the voltage drop between System Manager...

Страница 11: ...5 2 Alarm contact All PowerTaroms are equipped with a signal contact See illustration in chapter 6 4 to locate the terminals The signal relais switches if a system fault occurs under over voltage over...

Страница 12: ...nter the corresponding menu Other than this Main Menu the keys always have the normal functions described below to navigate through menus With the arrow keys you can scr parameters can be changed by t...

Страница 13: ...sing blocking diodes in the module cables In the System Manager there is a small data logger built in which can be used for a quick view of the energy allocation To conduct research where data of an e...

Страница 14: ...ated state of charge of the battery After entering this menu by pressing OK you may switch with the keys associated SOC in SOC 12V system 24V system 48V system 0 10 9 V 21 8V 43 6V 10 10 90 10 99V 21...

Страница 15: ...charge should be activated After having entered the window by pressing OK the first line shows Boost___voltage and you may alter the voltage appearing in the second line by pressing the arrow keys By...

Страница 16: ...disconnectio System Manager allows only these values for disconnect an difference of 0 8V 12V 1 6V 24V und 3 2 disconnection you must first increase Possibilities for programming by voltage r The char...

Страница 17: ...ogram the acid density and the equalizing charging equal charging When the configuration is set to these windows are not activated Battery Typ By pressing any one of the 4 keys under the cover you lea...

Страница 18: ...ow keys to avoid changing the values Hint If you have programmed a wrong value you will again reach the window with the undesired value by pressing the OK key a few times When you have reached the win...

Страница 19: ...ust be out of children s and unauthorized persons reach The basis on which controller is to be installed should not be easily flammable During operation the backside of the controller cooling body hea...

Страница 20: ...ndispensable to install a safety fuse directly on the battery pole This fuse sec For isolated systems it is not necessary not common or even not permitted by national laws to ground connect the compon...

Страница 21: ...ation of safety fuses Finally secure all cables within the controller s immediate surrounding by strain relieves All other components must also be strain relieved 7 5 Uninstalling Uninstall the regula...

Страница 22: ...bviously Even a discharge between clouds or a strike far can induce energy pulses into the elec conducting parts of the installation like wires structure or electronic components Not even a visible an...

Страница 23: ...GND GND GND lay grounding cables separately to the DC cables Inside protection zone protected photovoltaic field Outside protection zone unprotected photovoltaic field avoid loops between module cabl...

Страница 24: ...in and out the battery are calculated and displayed at this PowerTarom and his TarCom logger You only need one HS200 for the whole system Currents higher than the maximum of 200A will not layed but d...

Страница 25: ...2x M40 14 28mm 4x M32 12 21mm 1x M25 17mm t 12 2 le glands and t sink PowerTarom 2140 4110 and 4140 4x M40 14 28mm 2x M32 wo heat sinks 1mm 1x M25 8 17mm Weight 9 k 10 kg 9 kg 10 kg g 10kg Dimensions...

Страница 26: ...s the three left keys ok together to reset the display Module current The module current exceeds the max currents allowed Although this will not cause a defect The solar generator exceeds the nominal...

Страница 27: ...ties unprofessional installation or commissioning incorrect or negligent handling improper transport excessive loading use of improper equipment faulty construction work unsuitable construction locati...

Страница 28: ......

Отзывы: