5 Installation of the industrial control
5.1 Guidelines for the installation of the SE-707
Separate the SE-707 device from heat, high voltage, and electrical noise
As a general rule for laying out the devices of your system, always separate the devices that generate high voltage and high
electrical noise from the low-voltage, logic-type devices such as the SE-707.
When configuring the layout of the SE-707 inside your panel, consider the heat-generating devices and locate the electronic-
type devices in the cooler areas of your cabinet. Operating any electronic device in a high-temperature environment will
reduce the product life.
Consider also the routing of the wiring for the devices in the panel. Avoid placing low voltage signal wires and
communications cables in the same tray with AC power wiring and high-energy, rapidly-switched DC wiring.
5.2 General mounting instructions
All SE-707 devices are mounted from the front, i.e. in a control panel. They are fastened from the rear with the supplied
fixing frame and 2 securing nuts.
All SE-707 devices can be operated up to a maximum ambient temperature of 45°C. The ambient temperature stated applies
to the area in the direct vicinity of the lower connectors, if the device is mounted vertically with unimpeded air convection
and a maximum operating height of 2000 m above sea level. The cooling slots must always be free in order to ensure the
proper cooling of the system.
The device can be mounted in an enclosure if the ambient temperature is taken into consideration. Provide a wall clearance
of at least 50 mm on all sides of the housing, so that sufficient air circulation is ensured. A minimum clearance of 75 mm
from active elements such as load current supply, transformers etc. must be ensured.
Avoid the exposure of the flat screen to direct sunlight. The radiation from the sun (UV component) reduces the lifespan of
the LCD display.
ATTENTION !
The following must be ensured in order to prevent the device from overheating during operation:
-
The cooling slots must always be free in order to ensure the proper cooling of the system.
-
Avoid the exposure of the flat screen to direct sunlight.
-
The mounting angle must not exceed ± 35° from the vertical
If these conditions cannot be met, the mounting of an external fan is recommended.