Operating Instructions
IS1 PROFIBUS 3.00 E
- Technical alterations reserved -
65
PROFIBUS DP interface for IS1+
3.3.1.2 TIM (9480/... , 9481/...
, 9482/…)
Temperature measurement RTD, TC (1 Digit = 0,1 °C)
Temperature
Units
Range
Diagnosis messages
Decimal
hexadecimal
*1)
*1)
Line break /
Upper limit exceeded
*2)
*2)
*2)
Temperature measurement range
.
.
.
1000 °C
10000
2710
.
.
.
1 °C
10
000A
.
.
.
0 °C
0
0
-0,1 °C
-1
FFFF
.
.
.
-100 °C
-1000
FC18
.
.
.
*2)
*2)
*2)
*1)
*1)
Lower limit exceeded
/ short circuit
*2) The limits of the measurement range are pending on the parameterized input type (see Operating instructions IS1)
2 wire and 4 wire Resistance Measurement Pot in Ohm 500 R ...10K (module 9480 /.. , 9482/..)
Range
Units
%
Range
Diagnosis
messages
500 R
2 K 5
5 K
10 K
decimal hexadecimal
>588 R
>2,94 K
> 5,88K >11,76 K
*1)
*1)
Line break
588 R
2,94 K
5,88 K
11,76 K
32511
7EFF
117,6%
Over range
-
.
.
.
500 R
2 K 5
5 K
10 K
27648
6C00
100%
Nominal
range
-
.
.
.
250 R
1K250
2K5
5 K
13824
3600
50%
.
.
.
0 K
0 K
0 K
0 K
0
0
0%
3 wire and 4 wire Resistance Position Measurement Pot in % 500 R...10K (module 9480/.. , 9482/..)
Range
Units
%
Range
Diagnosis
messages
500R
2K5
5 K
10 K
decimal hexadecimal
>588 R
>2,94 K
>5,88 K
>11,76K
*1)
*1)
Line break
position 100 %
27648
6C00
100%
Nominal
range
-
.
.
.
position 50 %
13824
3600
50%
.
.
.
position 0 %
0
0
0%
< 50 R
< 250 R
< 500 R
< 1 K
*1)
*1)
short circuit
0,02 R
0,1 R
0,2 R
0,4 R
Resolution per Digit
Hint: 9480 supports no 4 wire Resistance Position Measurement in %.