PROFIBUS DP interface for IS1+
3.11 I&M Function (DPV1)
IS1+ supports the I&M (Identification and maintenance) function according PNO
specification and delivers the following I&M data on Index 255:
I&M0 on Index 255 / 65000, Read/Write:
Name
Size
Data Type
Content
Header
manufacturer specific
10 Octets
0x00 ( not used )
I&M Block
DEVICE_MAN_ID
2 Octets
Uint16
158 (0x9e)
ORDER_ID
20 Octets
Visible String e.g. ´ 9440/15-01-11´ ( STAHL Type No.)
SERIAL_NUMBER
16 Octets
Visible String e.g. ´ 115337-0004´
HARDWARE_REVISION
2 Octets
Uint16
e.g. ´F´ = 0x0046
*1)
SOFTWARE_REVISION
4 Octets
*2)
e.g. ´02-31´
*2)
REVISION_COUNTER
2 Octets
Uint16
0
PROFILE_ID
2 Octets
Uint16
0x0000
PROFILE_SPECIFIC_TYPE
2 Octets
Uint16
0x0000
IM_VERSION
2 Octets
2 Uint8
1.0
IM_SUPPORTED
2 Octets
Bit Array
0
(0x1E with 9442 CPU and GSE V4.xx or V5.xx)
*1)
HARDWARE_REVISION:
STAHL is using the letters ´A´ to ´X´ which are represented as characters (example: ´A´ = 0x0041).
*2)
SOFTWARE_REVISION:
example of allocation:
Stahl software revision:
V 02-31
Data Type
Char
Uint8
Uint8
Uint8
Data
´V´ = 0x56
0x02
0x1F
0x00
displayed
´V´
02
31
0
I&M1 on Index 255 / 65001, Read/Write:
Name
Size
Data Type
Content
Header
manufacturer specific
10 Octets
empty = 0 (not used)
I&M Block
TAG_FUNCTION
32 Octets
Visible String User specific data which is stored in the device.
Default: filled with ´0x20´ (blank)
TAG_LOCATION
22 Octets
Visible String
I&M1 to I&M4 supported by 9442 CPU only.