Operating Instructions
IS1 PROFIBUS 3.00 E
- Technical alterations reserved -
54
PROFIBUS DP interface for IS1+
3.2.4.2 UMH 9469
Byte
Hex
7
6
5
4
3
2
1
0
Bezeichnung
Wert
0
53
1
Diagnostic messages of the module
0 =Off
1 = On
0
0
1
Input Filter
0 = small
1 = medium
2 = big ( 50 Hz)
3 = big (60 Hz)
1
Scan HART Livelist
0 = Off
1 = On
0
Measurement range ac. NAMUR
0 = No
1 = Yes
1
Signal range
0 = 0-20 mA
1 = 4-20 mA
0
DI Pulse extension 1,2 s
0 =Off
1 = On
1
CC
1
0
0
Signal in case of error S 0
0 = -10 % (live zero only) / 0
1 = 0 % / 0
2 = 100 % / 1
3 = AI Status Code / AO 110% / 1
4 = AI Status Code / AO 0% / 0
6 = freeze (initial value 0% / 0 )
7 = freeze (initial value 100% / 1 )
1
Error detection S 0
0 = Off
1 = On
1
0
0
Signal in case of error S 1
1
Error detection S 1
2
CC
1
0
0
Signal in case of error S 2
1
Error detection S 2
1
0
0
Signal in case of error S 3
1
Error detection S 3
3
CC
1
0
0
Signal in case of error S 4
s. a.
1
Error detection S 4
1
0
0
Signal in case of error S 5
1
Error detection S 5
4
CC
1
0
0
Signal in case of error S 6
1
Error detection S 6
1
0
0
Signal in case of error S 7
1
Error detection S 7
5
00
0
0
Connection S0
0 = 2 wire analog
0
0
Connection S1
1-3 = Reserved
0
0
Connection S2
0
0
Connection S3
6
00
0
0
Connection S4
0 = 2 wire analog
0
0
Connection S5
1 = 3/4 wire analog (Input only)
0
0
Connection S6
2 = 2/3 wire digital
0
0
Connection S7
3 = Reserved
7
88
1
0
0
0
Input No. HART device for pos. 1
0…7
1
0
0
0
Input No. HART device for pos. 2
8 = ´not used ´
8
88
1
0
0
0
Input No. HART device for pos. 3
(9
– 15 Reserved)
1
0
0
0
Input No. HART device for pos. 4
9
55
0
1
No. HART variable for pos. 1
0 = HART Variable No. 1
0
1
No. HART variable for pos. 2
1 = HART Variable No. 2
0
1
No. HART variable for pos. 3
2 = HART Variable No. 3
0
1
No. HART variable for pos. 4
3 = HART Variable No. 4
10
88
1
0
0
0
Input No. HART device for pos. 5
0…7
1
0
0
0
Input No. HART device for pos. 6
8 = ´ not used ´
11
88
1
0
0
0
Input No. HART device for pos. 7
(9
– 15 Reserved)
1
0
0
0
Input No. HART device for pos. 8
12
55
0
1
No. HART variable for pos. 5
0 = HART Variable No. 1
0
1
No. HART variable for pos. 6
1 = HART Variable No. 2
0
1
No. HART variable for pos. 7
2 = HART Variable No. 3
0
1
No. HART variable for pos. 8
3 = HART Variable No. 4
13
00
0
Signal type S 0
0 = Input
0
Signal type S 1
1 = Output
…
0
Signal type S 7
Signal in case of error for DI/DO: 0%, -10%
= 0,
100%, 110%
= 1