Operating Instructions
IS1 PROFIBUS 3.00 E
- Technical alterations reserved -
92
PROFIBUS DP interface for IS1+
PROFIsafe status
Byte
Value
Diagnosis Text
Diagnosis Help Text
Hex
Dec
n+5
0x40
64
F_Dest_Add mismatch
Mismatch of safety destination address
0x41
65
F_Dest_Add not valid
Safety destination address not valid
0x42
66
F_Source_Add not valid
Safety source address not valid
0x43
67
F_WD_Time not defined
Safety watchdog time value is 0 ms
0x44
68
F_SIL parameter error
Parameter „F_SIL“ exceeds SIL from specific device application
0x45
69
F_CRC_Length error
Parameter „F_CRC_Length“ does not match the generated values
0x46
70
F-Param. version error
Version of F-Parameter set incorrect
0x47
71
CRC1-Fault
CRC1-check of received F-data failed