Operating Instructions
IS1 PROFIBUS 3.00 E
- Technical alterations reserved -
71
PROFIBUS DP interface for IS1+
Data
Data
Byte
all DIM
(947x/3x in compatible mode)
DIOM 9470/3x, 9471/35, 9472/35
(IS1+)
Type
DIM
DIM
+Stat
DIM
+2CF
DIM
DI/DO
DI/DO
+2CF
DI/DO
+6CF
DI/DO
+8CF
Input
1
DI signals 0
– 7 *1)
UINT16
2
DI signals 8
– 15 *1)
3
Signal Status 0
– 7
4
Signal Status 8
– 15
5 + 6
C/F I14
C/F S15
C/F S15
C/F S15
UINT16
(UINT32)
7 + 8
C/F I15
C/F S14
C/F S14
C/F S14
9 + 10
-
-
-
-
-
-
C/F S13
C/F S13
11+12
C/F S12
C/F S12
13+14
C/F S11
C/F S11
15+16
C/F S10
C/F S10
17+18
-
C/F S9
19+20
C/F S8
Output
1
-
-
*2)
-
DO 0 - 7
DO 0 - 7
DO 0 - 7
DO 0 - 7
UINT16
2
-
DO 8 - 15
DO 8 - 15
DO 8 - 15
DO 8 - 15
3
-
Reset
C14-15
Reset
C10-15
Reset
C8-15
UINT8
4
Start/Stop
C14-15
Start/Stop
C10-15
Start/Stop
C8-15
*1) In operation mode DI/DO and parameterization as DO written output values can be read back via the
dedicated DI signals.
In operation mode DI/DO and parameterization as DI the dedicated DO signals have no effect.
Output Data
DI/DO+xCF
*2) Output Data
DIM+2CF:
Byte
Bit
Function
1
0
Reset Counter S14
0 = Run,
1 = Reset (Counter = 0)
1
Reset Counter S15
2
Start/Stop S14
0 = Counter Run,
1 = Counter Stop
3
Start/Stop S15
4 - 7
0 (Reserved)
-
Byte
Bit
DO
Reset Counter
Start/Stop Counter
see
above
0
DO 0 / 8
0 = output high
Impedance
(actuator = Off)
1 = output is
powered
( actuator = On )
Reset C8
0 = Run,
1 = Reset
(Counter=0)
Start/Stop C8
0 = Counter Run
1 = Counter Stop
1
.
Reset C9
Start/Stop C9
. .
.
. .
. .
6
.
Reset C14
Start/Stop C14
7
DO 7 / 15
Reset C15
Start/Stop C15
!