Operating Instructions
IS1 PROFIBUS 3.00 E
- Technical alterations reserved -
56
PROFIBUS DP interface for IS1+
3.2.4.4 TIM mV 9481
Byte
Hex
7
6
5
4
3
2
1
0 Parameter
Value
0
01
1
Diagnostic messages of the module
0 = Off
1 = On
0
Input Filter
0 = 50 Hz
1 = 60 Hz
0
0
0
0
0
0
Not used
1
BB
0
1
1 Signal in case of error I 0
3 = Status code
6 = freeze (Init. value 0%)
1
Error detection I 0
0 = Off
1 = On
0
1
1
Signal in case of error I 1
1
Error detection I 1
2
BB
0
1
1 Signal in case of error I 2
1
Error detection I 2
0
1
1
Signal in case of error I 3
1
Error detection I 3
3
BB
0
1
1 Signal in case of error I 4
1
Error detection I 4
0
1
1
Signal in case of error I 5
1
Error detection I 5
4
BB
0
1
1 Signal in case of error I 6
1
Error detection I 6
0
1
1
Signal in case of error I 7
1
Error detection I 7
5
00
0 Input signal I 0
0 = Balanced
0
Input signal I 1
1 = Unbalanced
0
Input signal I 2
0
Input signal I 3
0
Input signal I 4
0
Input signal I 5
0
Input signal I 6
0
Input signal I 7
6
44
0
1
0
0 Type I 0
0 = 0…100 mV
1 = THC Type B
0
1
0
0
Type I 1
2 = THC Type E
3 = THC Type J
7
44
0
1
0
0 Type I 2
4 = THC Type K
5 = THC Type N
0
1
0
0
Type I 3
6 = THC Type R
7 = THC Type S
8
44
0
1
0
0 Type I 4
8 = THC Type T
9 = THC Type L
0
1
0
0
Type I 5
10 = THC Type U
11 = THC Type XK (L)
9
44
0
1
0
0 Type I 6
(12…15 = reserved)
0
1
0
0
Type I 7
10 .. 13
00
Not used