Operating Instructions
IS1 PROFIBUS 3.00 E
- Technical alterations reserved -
85
PROFIBUS DP interface for IS1+
Device related diagnosis IS1+ Fieldstation (DPV0)
Byte
Bit
Value / Info Message / Function
Measure / Remedy
CPU Status
(NE107)
6
-
0x14
Header Byte
-
-
-
7
0
CPU
Diagnosis-
data
Error in IS1 parameters from
DP master
Check parameter setting in DP
master.
Failure
1
Error in IS1 configuration data
from DP master
Check configuration data in DP
master
2
Version conflict GSE/CPU
Version conflict of GSE file and
CPU Firmware. Use GSE file
compatible to CPU Firmware.
3
Redundancy Parameterization PM:
OK / red. PM observation is
deactivated
Parameter ´Red. PM = Yes´ shall
be enabled if red. PM are plugged.
Main-
tenance
Required
4
Slot address error CPU
The CPM has detected an incorrect
change of the slot address during
operation. -> Exchange CPM
5
9440: red. CPU descr. Required
9442: Redundancy
Parameterization CPU: OK / red.
CPU observation is deactivated
9440: Change configuration.
9442: Parameter ´Red. CPU =
Yes´ shall be enabled if red. CPU
are plugged.
6
Failure CPU-L
Check PM supply voltage.
CPU exchange required if OK.
Failure
7
Failure CPU-R
8
0
Line-
redundancy
(9440 only)
X1: receive from AS disturbed
Check: Bus connections, Bus
wiring, Termination, Fieldbus
isolating repeater …
Main-
tenance
Required
1
X2: receive from AS disturbed
2
X1: transmit to AS disturbed
3
X2: transmit to AS disturbed
4
9442
CPU
only
*1)
Failure PM-L
Check PM supply voltage.
PM exchange required if OK.
Failure
5
Failure PM-R
6
Socket backup memory
disturbed.
System operation till next
Power On/CPU Reset is
possible. Socket exchange is
required on next operation stop.
Main-
tenance
Required
7
CPU
redundancy
Backup CPU not available
(Message of CPM Redundancy from
9440 Firmware V0x-42 and from
GSE V1.25, V2.25 or V3.03)
Check:
- Bus connection of red. CPU
- Function of red. CPU
- Rail connection between red.
CPUs
9
0
9442
CPU
only
*1)
Temperature Alarm
CPU / PM
Ambient temperature around the
CPU or PM is out of spec.
In case of overtemperature reduce
ambient temperature or increase
ventilation, shadowing .…
Out of
Spec.
1
PM overload
Reduce PM load!
2
Maintenace Request CPU-L
Exchange of module
recommended due to operating
conditions.
Main-
tenance
Required
3
Maintenace Request CPU-R
4
Maintenace Request PM-L
5
Maintenace Request PM-R
6
Slot address error PM-L
The module has detected an
incorrect change of the slot
address during operation. ->
Exchange PM and send it back to
STAHL.
7
Slot address error PM-R
*1) 9442 CPU with GSE Files from V2.34 only.