Operating Instructions
IS1 PROFIBUS 3.00 E
- Technical alterations reserved -
14
PROFIBUS DP interface for IS1+
2.3 System requirements
Hardware requirement CPM/CPU:
CPM 9440/12-01-11 (24V Z1 Stahl)
as of Revision F
CPM 9440/15-01-11 (24V Z2 Stahl)
as of Revision F
CPM 9440/22-01-11 (24V Z1 PNO) all Revisions
CPM 9440/22-01-21 (230V Z1 PNO) all Revisions
CPU 9442/xx-01-11 (Z2)
all Revisions
Software requirements:
9442 CPU:
All CPU FW Revisions together with IS1 IO-Module from FW 02-00
or IS1+ IO-Module
(94xx/3x….) from FW 03-01
Older IS1 IO-Modules with firmware 01-xx can be operated with 9440 CPUs only!
GSE File selection see
9440 CPM:
IO-
Module
FW
DPV0 operation
without C2 communication
DPV1 operation
with C2 communication
DPV0
Diagnosis
DPV1 Diagnosis
DPV0 Diagnosis
DPV1 Diagnosis
IS1 IO-
Module
01-xx
GSE V1.xx
-
GSE V1.xx
-
from
02-00
CPM FW from
V01-32
CPM FW from
V01-41
CPM FW from V02-41, 03-41 or 09-41
GSE from V2.00
GSE from V3.00
GSE from V2.00
GSE from V3.00
IS1+ IO-
Module
(94xx/3x….)
from
03-01
CPM FW from V01-47
CPM FW from V02-47, 03-47 or 09-47
GSE from V2.32
GSE from V3.10
GSE from V2.32
GSE from V3.10
Software requirements for CPM Redundancy see:
The IS1+ Remote I/O-system with PROFIBUS DPV1 supports the following additional functions:
PROFIBUS according DPV1
-
Diagnosis status messages
-
I&M Functions
Support of PROFIsafe I/O modules (9440 CPM only)
HART communication
Support of IS1 DTMs (FDT) with communication via DPV1