Operating Instructions
IS1 PROFIBUS 3.00 E
- Technical alterations reserved -
97
PROFIBUS DP interface for IS1+
3.10 DPV1 records
Following DPV1 records are supported:
Slot
write_ind read_ind
Telegram transaction
Description
[DS Index]
[DS Index]
0
(CPU)
255 -> 65000
255
write_ind -> read_ind
I&M0 Function
…
…
…
I&M1 … I&M3
Supported by 9442 CPU only
255 -> 65004
255
write_ind -> read_ind
I&M4 Function
-
7
read_ind
HART Livelist
8
8
write_ind -> read_ind
Servicebus protocol tunneling via DPV1
-
9
read_ind
Readback of adjusted ´F-Destination address´ of all
PROFIsafe I/O modules
-
129
read_ind
HART Parameter
-
148
read_ind
HART DS Information
-
149
read_ind
HART Feature Flags
1-16
(IOM)
255 -> 65000
255
write_ind -> read_ind
I&M0 Function
…
…
…
I&M1 … I&M3
Supported by 9442 CPU only
255 -> 65004
255
write_ind -> read_ind
I&M4 Function
-
129
read_ind
HART Parameter
-
148
read_ind
HART DS Information
-
149
read_ind
HART Feature Flags
80
81
write_ind -> read_ind
with delayed response
HART transaction channel 0
82
83
HART transaction channel 1
84
85
HART transaction channel 2
86
87
HART transaction channel 3
88
89
HART transaction channel 4
90
91
HART transaction channel 5
92
93
HART
transaction channel 6
94
95
HART transaction channel 7
Structure of HART records according PNO Spec. 2.312
Structure of I&M records according PNO Spec. 3.502
Structure of HART Livelist and Servicebus Protocol according Stahl specification. -> Access via IS1 DTM
Even when using multiple parallel C2 channels only one HART telegram processing is supported at a time.