Operating Instructions
IS1 PROFIBUS 3.00 E
- Technical alterations reserved -
68
PROFIBUS DP interface for IS1+
3.3.1.3 AOM 0
– 20 mA (9465/... , 9466/..., 9468/..)
Measuring
range
0
– 20 mA
Units
%
Range
Decimal
Hexadecimal
*1)
>30137
>75B9
21,8 mA
30137
75B9
109%
Over range
.
.
.
20 mA
27648
6C00
100%
Nominal range
.
.
.
10 mA
13824
3600
50%
.
.
.
0 mA
0
0
0%
0 mA
< 0
< 0
AOM 4
– 20 mA
Measuring
range
4
– 20 mA
Units
%
Range
Decimal
Hexadecimal
*1)
>30759
>7827
21,8 mA
30759
7827
111,25%
Over range
.
.
.
20 mA
27648
6C00
100%
Nominal range
.
.
.
12 mA
13824
3600
50%
.
.
.
4 mA
0
0
0%
3,999 mA
-1
FFFF
Under range
0 mA
-6912
E500
-25%
0 mA
< -6912
< E500
*1) :
The AOM attempts to increase the current further according to the control value. However, depending
on the burden effective resistance, the maximum output voltage of the AOM may be reached whereby
the current can no longer be increased.
Safety position after Power On:
After Power On of the CPU the data area of the outputs is initialized with the value -32768 (0x8000) as signal
for the safety position.
The outputs remain in the save position as long as the allocated register is overwritten with a valid output value
( <> -32768 (0x8000)) from AS or from IS Wizard.
(see also chapter 3.4.2)