DPU/DO - Page 38 - REV. 5/25/00
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
* * S e t P a r a m e t e r s F o r U n i t - 1 * *
- - - > O P T I O N R E G I S T E R 1 - N I G H T P A R K
( 0 ) O f f ( 2 ) R S ( 4 ) L C ( 6 ) A C
( 1 ) L S * ( 3 ) A S ( 5 ) R C
U s e < > t o S e l e c t O p t i o n
U s e < N U M B E R > t o S e t O p t i o n
< S A V E > t o S a v e < E S C A P E > t o E x i t
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
-- Option Register 1 Night Park Parameter Screen --
This determines the function of the module when jumper J23 option 1 is closed on the carriage controller
(usually generated by the building management system normally closed contacts, interfaced to only one
controller per module - see drawing 480268.001). Locked aisles are reset and safeties remain active.
0 - Option Jumper Disabled - nothing happens when the hardware jumper is closed.
1 - Module closes to the left, evenly spaces carriages, deactivates controls, remains parked.
2 - Module closes to the right, evenly spaces carriages, deactivates controls, remains parked.
3 - Alternates direction closing, evenly spaces carriages, deactivates controls, remains parked.
4 - Module closes to the left, deactivates control heads, remains parked.
5 - Module closes to the right, deactivates control heads, remains parked.
6 - Module alternates direction closing, deactivates control heads, remains parked.
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
* * S e t P a r a m e t e r s F o r U n i t - 1 * *
- - - > O P T I O N R E G I S T E R 2 - F I R E P A R K
( 0 ) O f f * ( 2 ) R S ( 4 ) L C
( 1 ) L S ( 3 ) A S ( 5 ) R C
U s e < > t o S e l e c t O p t i o n
U s e < N U M B E R > t o S e t O p t i o n
< S A V E > t o S a v e < E S C A P E > t o E x i t
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
-- Option Register 2 Fire Park Parameter Screen --
This determines the function of the module when jumper J23 option 2 is closed on the carriage controller
(usually by the building management system normally closed contacts, interfaced to only one controller
per module - see drawing 480268.001). Locked aisles are reset and safeties remain active. Note: EC400
control heads remain functional to allow fire fighting personnel access after parking.
0 - Option Jumper Disabled - nothing happens when the hardware jumper is closed.
1 - Module closes left, evenly spaces carriages, deactivates heads.
2 - Module closes right, evenly spaces carriages, deactivates heads.
3 - Module alternate direction closing, evenly spaces carriages, deactivates heads.
4 - Module closes to the left, deactivates heads.
5 - Module closes to the right, deactivates heads.
On version 4.7 & later; stationary carriages are made moveable for both Night and Fire Park modes.