DPU/DO - Page 32 - REV. 5/25/00
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
* * S e t P a r a m e t e r s F o r U n i t - 1 * *
- - - > A I S L E L I G H T A C T I V A T I O N
* ( 0 ) N o t I n s t a n t O n
( 1 ) I n s t a n t O n
U s e < > t o S e l e c t O p t i o n
U s e < N U M B E R > t o S e t O p t i o n
< S A V E > t o S a v e < E S C A P E > t o E x i t
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
-- Aisle Light Activation Parameter Screen --
This is the first of several parameters that control the operation of module lighting. If set to Not
Instant On (Delayed On), the lights will only turn on in the requested aisle after the movement
cycle is complete and all carriages have stopped. If set to Instant On, the lights will turn on in
the requested aisle as soon as movement begins or shortly there after.
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
* * S e t P a r a m e t e r s F o r U n i t - 1 * *
- - - > A I S L E / B A Y L I G H T T I M I N G
* ( 0 ) N o t T i m e d
( 1 ) T i m e d
U s e < > t o S e l e c t O p t i o n
U s e < N U M B E R > t o S e t O p t i o n
< S A V E > t o S a v e < E S C A P E > t o E x i t
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
-- Aisle/Bay Light Timing Parameter Screen --
Aisle lights that are set to Not Timed will remain on until the user presses the reset button at the
open aisle or requests another aisle. If set to be timed aisle lights will turn off after their set
period of time. In most cases activating a sweep, aisle entry, safety floor, ZFS or pushing an
Open Aisle button will reinitialize the timer to its set value. Whether set for timed or not timed,
pushing reset at the open aisle will turn the aisle lights off.
Bay lights that are set for not timed will remain on until the user presses the last accessed aisle
reset button and allows the set bay light time-out to expire (EC400 turns off immediately after
pushing reset). When set to be timed the bay lights will turn off after their corresponding set
period of time. In most cases activating a sweep, aisle entry, safety floor, ZFS or pushing an
Open Aisle button will reinitialize the bay light timer to its set value.
If this screen is set for "Not Timed,” the next screen will not be displayed.