Installation Guide
Page 27 of 53
6.1.5
Running external wiring into the enclosure
Figure 10: Drilling marks
Use the drilling markings on the enclosure to drill the required cable entry holes.
Bring external cables into the enclosure.
-
Grid supply
-
Backup supply
-
Modbus
-
Ethernet
Secure cable entry holes with appropriate cable glands to seal the entry holes in
accordance with AS/NZS 3000.
The AC WAGO terminal accepts copper only sizes up to 16 mm
2
(6 AWG)
The PE WAGO terminal accepts copper only sizes up to 16 mm
2
(6 AWG)
Touch current over limit 3.5 mA when earth fault condition
present.