Installation Guide
Page 22 of 53
6
Mounting and electrical installation
Electrical work on the storage system and electrical
distributor
Danger to life due to electrocution!
Switch off the storage system to electrically isolate it.
Disconnect the relevant electrical circuits.
Secure against anyone switching on the device again.
Wait five minutes so the capacitors can discharge.
Check that the device is disconnected from the power
supply.
Only licensed electricians are permitted to carry out
electrical work.
Working on the electrical distributor
Touch voltage in the event of fault
Danger to life due to electrocution!
Observe maximum line lengths
The communication lines connected to the storage system
(mains line, Ethernet line, other data lines) are NOT allowed to
exceed a maximum length of 50 meters.
RCD protection
If the local regulation requires an external RCD protection, a
type A or B RCD 30mA can be used. For applications, where an
external PV inverter is installed in the backup path, a 100mA
rated RCD is recommended.
In addition, the installation of the
system must comply with all relevant Australian standards
including AS/NZS 3000, AS/NZS 4777.1, AS/NZS 5033 and
AS/NZS 5139.