Installation Guide
Page 14 of 53
Safety
Protection class
I / PE conductor
Overvoltage category
III
Degree of protection
IP 56
Rated short-withstand current (ICW)
1.5 kA
Ambient conditions
Environment
Outdoor
Storage temperature range
0 °C ... 40 °C
Transport temperature range
-15 °C ... 50 °C
Max. rel. humidity
90 %, non-condensing
Permissible installation altitude
2,000 m above sea level
Pollution degree
3
Backup specification
Nominal backup current (Continuous)
22 A
Nominal output voltage
230 V
Nominal power
5000 W
Nominal frequency
50 Hz
Max backup power (Max 30mins)
5300 VA
Max backup power (Max 60s)
7050 VA
Max backup power (Max 300ms)
7600 VA
Maximum compatible PV inverter
6 kW
Certifications
Grid connections
AS/NZS 4777.2:2020
EMC / EMI protection
EN 61000-6-1, EN 61000-6-3,
IEC 62040-2
Safety
IEC 62040-1, IEC 62477-1, IEC
62619, IEC 62109-1, IEC 62109-2
Additional ambient conditions:
-
The installation location must not be at risk of flooding.
-
Installation room should be ventilated.
-
All applicable building codes must be observed.
-
Even floor, suitable for heavy loads.
-
Observe fire control standards.
-
Free from corrosive and explosive gases (ammonia content max. 20 ppm).
-
Free from dust (especially flour dust or sawdust).
-
Free from vibrations.
-
Free access to the installation location.
-
If possible, no direct sunlight.