80
10�2 System Switching Off
Proceed as follows to switch off the system:
1. Enable the inverter stand-by by placing the ON/OFF switch in the “0” position.
2. Disconnect the DC switch (position 1).
3. Disconnect the AC GRID and EPS (if present) circuit breakers.
4. Disconnect the BATTERY circuit breaker (where present) and turn off the HV battery.
5. Wait for the display to turn off.
10�3 Uninstall
DANGER!
Fatal electric shock hazard!
In daylight the PV generator supplies the inverter with a dangerously high DC
voltage.
■
Make sure that all electrical input conductors to the inverter are de-energized
before starting any work on the inverter or the input conductors.
1. Proceed as follows to uninstall the system:
2. Disconnect the battery cable connectors from the BAT inputs.
3. Disconnect the DC connectors of the photovoltaic panel strings from the inputs PV1 and
PV2.
4. Open the connection compartment by removing the fixing screws.
5. Disconnect the AC GRID and EPS (if present) conductors.
6. Disconnect the communication wires and external controls where present
7. The ES-T can now be removed for disposal or repair.