27
en
NOTE
■
Make sure to be compliant with the local regulations.
■
Make sure to be compliant with the grid code of the distribution network
operator.
■
The connection of multiple inverters to the public grid must comply with cur-
rent legislation relating to maxi-mum power imbalance.
The power losses on the AC GRID line must be less than 1% of the rated power. The indicative
data of the connection are reported below:
Wire cross-section
Line maximum length
5ES-T
6ES-T
8ES-T
10ES-T
2.5 mm2
18 m
12 m
4.0 mm2
29 m
19 m
6.0 mm2
45 m
30 m
Connection instructions for AC Output Cables
6. Remove the cover of the connection compartment by removing the screws as shown in
the figure below:
Fig. 12: Removing the cover of ES-T
7. Connect the phase (L1, L2, L3), neutral (N) and earth (PE) wires of the AC grid input to the
GRID terminal block respecting the correct assignment:
Cable
Terminal
Phase (L1)
L1 terminal
Phase (L2)
L2 terminal
Phase (L3)
L3 terminal
Neutral (N)
N terminal
Earth (PE)
PE terminal