IT
ALIANO
ENGLISH
54
IOMMASGPXX00-GB_01
Green Power
100-120 kVA
Battery alarm.
•
General battery alarm due to: battery test failed, maximum battery voltage, battery circuit breaker open, battery
charger failure. Check for other alarms and inspect the batteries.
Battery room.
•
This alarm is generated when the battery room temperature, measued with an external sensor, is higher than
the permitted maximum. Check the displayed temperature, and check the battery room ventilation/conditioning
system.
Batteries exhausted.
•
This alarm is generated when the batteries’ charge is low and the UPS is about to switch off . Check for other
alarms.
Battery circuit open.
•
Battery circuit breaker open.
Rectifi er protection.
•
The machine room temperature is above the recommended maximum. Check the UPS room ventilation/condi-
tioning system.
Inverter protection.
•
The machine room temperature is above the recommended maximum. Check the UPS room ventilation/condi-
tioning system.
Bypass protection.
•
This alarm is generated when the bypass has reached the maximum permitted overload time or in case of prob-
lems when switching from inverter to bypass. Check for other alarms. In case of overload, check the UPS’s load
and reset the alarms.
Common protection.
•
Incorrect confi guration parameters. Contact Aftersales Service.
Maximum ambient T°.
•
The machine room temperature is above the recommended maximum. Check the UPS room temperature and
ventilation/conditioning system. If there is a fan alarm, contact Aftersales Service.
Preventive maintenance.
•
The UPS must be checked periodically by Aftersales Service to ensure maximum effi ciency and performance. If the
alarm displays, the UPS must be inspected by a qualifi ed technician.
Incorrect use.
•
This alarm is not generated by a failure or fault, but by incorrect use or sizing of the UPS system. The alarm may
be tripped by:
TROUBLESHOOTING
9
Содержание Green Power 100
Страница 1: ...INSTALLATION AND OPERATING MANUAL Green Power 100 120 kVA ...
Страница 2: ......
Страница 42: ...ITALIANO ENGLISH 42 IOMMASGPXX00 GB_01 Green Power 100 120 kVA MIMIC PANEL 6 6 4 1 6 6 4 1 8 6 4 1 7 6 4 1 9 ...
Страница 64: ...FRANÇAIS ...